4 Operating Conditions
JetWeb
26
Jetter AG
Mechanical Operating Parameters
Parameter
Value
Reference
Free Falls
Withstanding Test
Height of fall (units within
packing): 1 m
DIN EN 61131-2
DIN EN 60068-2-32
Vibration Resistance
10 Hz - 57 Hz: with an amplitude
of 0.0375 mm for continuous
operation (peak amplitude of
0.075 mm)
57 Hz - 150 Hz: 0.5 g constant
acceleration for continuous
operation (1 g constant
acceleration as peak value), 1
octave per minute, 10 frequency
sweeps (sinusoidal), all spatial
axes
DIN EN 61131-2
IEC 06.02.1968
Shock Resistance
15 g occasionally, 11 ms,
sinusoidal half-wave, 2 shocks in
all three spatial axes
DIN EN 61131-2
IEC 68-2-27
Class of Protection
IP20, rear: IP10
DIN EN 60529
Mounting Position
Any position, snapped on DIN
rail
Operating Parameters - Electrical Safety
Parameter
Value
Reference
Protection class
III
DIN EN 61131-2
Dielectric Test
Voltage
Functional ground is connected
to chassis ground internally.
DIN EN 61131-2
Overvoltage
Category
II
DIN EN 61131-2
EMC - Emitted Interference Operating Parameters
Parameter
Value
Reference
Rack
Frequency 30 - 230 MHz,
limit 30 dB (µV/m) at 10 m
distance
frequency band 230 -
1,000 MHz, limit 37 dB (µV/m) at
10 m distance
(class B)
DIN EN 50081-1
DIN EN 55011
DIN EN 50081-2
Содержание JX2-IO16
Страница 10: ...Table of Contents JetWeb 10 Jetter AG...
Страница 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Страница 22: ...2 Introduction JetWeb 22 Jetter AG...
Страница 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Страница 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Страница 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Страница 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Страница 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Страница 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Страница 106: ...Appendices JetWeb 106 Jetter AG...
Страница 123: ...JX2 IO16 Appendix Jetter AG 123...