Voltage measurement
3-phase 4-conductor systems with rated voltages up to
480 VLN / 830 VLL (+/-10%) according to IEC
347 VLN / 600 VLL (+/-10%) according to UL
3-phase 3-conductor systems (grounded) with rated voltages up to
830 VL-L (+/-10%) according to IEC
600 VL-L (+/-10%) according to UL
3-phase 3-conductor systems (non-grounded) with rated voltages
up to
690 VL-L (+/-10%) according to IEC
600 VL-L (+/-10%) according to UL
Overvoltage category
· 1000 V CAT III according to IEC
· 600 V CAT III according to UL
Rated surge voltage
8 kV
Protection of the voltage measurement
1 - 10 A tripping characteristic B (with IEC/UL approval)
Measuring range L-N
0
1)
.. 720 Veff (max. overvoltage 1000 Veff )
Measuring range L-L
0
1)
.. 1000 Veff (max. overvoltage 1000 Veff )
Measuring range N-PE
up to 100 V
Resolution
16 bit
Crest factor
1.6 (referred to measuring range 600 V L-N)
Impedance
4 MΩ/phase
Power consumption
approx. 0.1 VA
Sampling frequency
51.2 kHz
Frequency of fundamental oscillation
- Resolution
40 Hz .. 70 Hz
0.01 Hz
Harmonics
1 .. 127.
1) ... The device only measures if at least one voltage measurement input has an L-N voltage of > 10 Veff
or an L-L voltage of > 18 Veff present.
Current measurement (../1 A) (../5 A)
Nominal current
5 A
Channels
8
· 2 systems - L1, L2, L3, N (optional)
· Single channels
Measurement range
0.005 .. 6 Aeff
Crest factor (relative to nominal current)
1.98
Overload for 1 s
120 A (sinusoidal)
Resolution
0.1 mA (color graphic display 0.01A)
Overvoltage category
300 V CATII
Rated surge voltage
2.5 kV
Power consumption
approx. 0.2 VA (Ri = 5 m
Ω
)
Sampling frequency
25.6 kHz
Harmonics
1 .. 63