UMG 801
www.janitza.de
72
Abb.
Assistant for configuring the digital outputs (GridVis
®
software)
12.2 4 digital outputs
The 4 digital outputs of the device are used to
produce pulses for counting the energy consump-
tion. The current measuring channels of the basic
device (or the selected module) are used as a ref-
erence in the form of measurement groups (mea-
surement group 1 - I1 to I4, measurement group
2 - I5 to I8, measurement group 3 - multifunction
channels).
In the “Peripherals" section of the "Configura-
tion" window in the GridVis
®
software, an assis-
tant guides you through the configuration of the
4 digital outputs with the following settings and
functions:
1.
Segment selection list
Selection of the device (basic device/modules).
2.
Measurement Group selection list
-
Selection of the measurement group of the
respective device.
3.
Measured Value selection list
-
Selection of the measured value, e.g. active en-
ergy overall tariff, apparent energy overall tariff,
reactive energy overall tariff, etc.
4.
Phase/Channel
-
Phase/channel whose pulse is used for the
output.
5.
Pulse valency -
See description for "Pulse output".
6.
Pulse width (pulse duration) -
See description „Pulse duration/pulse pause.“
on page 71.
INFORMATION
For detailed information on configuring the digital
outputs of your device, refer to the online help for
the GridVis
®
software.