18.2 Procedure in the event of a malfunction
Failure mode
Cause
Remedy
No display
External fuse for the supply voltage has
tripped.
Replace fuse.
No current display.
No measured voltage connected.
Connect measured voltage.
No measured current connected.
Connect measured current.
Displayed current is
too great or too small.
Current measurement on the wrong phase.
Check connection and correct if necessary.
Current transformer factor incorrectly pro-
grammed.
Read and program the current transformer
ratio on the current transformer.
Current harmonic exceeds current peak value
at measuring input.
Install current transformer with larger current
transformer ratio.
The current at the measuring input is too low.
Install current transformer with smaller current
transformer ratio.
Displayed voltage is
too high or too low.
Measurement on the wrong phase.
Check connection and correct if necessary.
Voltage transformer programmed incorrectly.
Read the voltage transformer ratio on the
voltage transformer and program.
Displayed voltage
is too low.
Overrange.
Use a voltage transformer.
The voltage peak value at the measuring input
was exceeded due to harmonics current.
Attention! Make sure that the measuring
inputs are not overloaded.
Incorrect display "Inductive/
capacitive phase shift"
Current path assigned to the wrong voltage
circuit.
Check connection and correct if necessary.
Active power consumed/
delivered is reversed.
At least one current transformer connection is
reversed.
Check connection and correct if necessary.
One current path assigned to the wrong volt-
age circuit.
Check connection and correct if necessary.
Active power too small or too
great.
Incorrectly programmed current transformer
ratio.
Read and program the current transformer
ratio on the current transformer.
Current path assigned to the wrong voltage
circuit.
Check connection and correct if necessary.
Incorrectly programmed voltage transformer
ratio.
Read the voltage transformer ratio on the
voltage transformer and program.
An input/output is not
responding.
Incorrectly programmed input/output.
Check programming and correct if necessary.
Incorrectly connected input/output.
Check connection and correct if necessary.
“Overrange" display
The measuring range has been exceeded.
Check connection and correct if necessary.
Correct current/voltage transformer ratio.
No connection to the device
OPC UA:
- Incorrect IP address/port
- Correct the IP address/port.
RS-485:
- Incorrect device address
- Different bus speeds (baud rate) and/or data
frames.
- Incorrect protocol.
- No termination.
- Correct the device address.
- Correct the speed (baud rate). Correct the data
frame.
- Correct the protocol.
- Terminate bus with termination resistor.
Despite the above measures,
the device does not function.
Device defective.
Send the device and error description to the
manufacturer for inspection.
ATTENTION
Material damage due to overloaded measuring inputs!
Too high current and voltage values overload the measuring inputs and can damage the device.
·Adhere to the limit values specified on the rating plate and in the technical data starting on
page 96!
·
Check your installation and connections!
Содержание UMG 801
Страница 9: ...www janitza de UMG 801 9...
Страница 31: ...www janitza de UMG 801 31...
Страница 47: ...www janitza de UMG 801 47...
Страница 91: ...www janitza de UMG 801 91...
Страница 105: ...www janitza de UMG 801 105...