UMG 801
63
·Press function button 1
ESC
to open the menu.
·Use buttons 2 “
5
” and 5 “
” to select the menu
item
Configuration
and confirm with button 3
Enter
.
·The
Configuration
window appears.
·In the
Configuration
window, use buttons 2
“
5
” and 5 “
” to select the menu item
Current
transformers
and confirm with button 3
Enter
.
·The
Current transformers
window appears.
INFORMATION
You can also configure current and voltage
transformer ratios in the device configuration
of the
Software GridVis
®
. A description of the
configuration in the software can be found in the
corresponding online help and tutorials.
·In the
Current transformers
window, choose the
Fig. Window Configuration -> item Current transformer
Ethernet (TCP/IP)
Fieldbus
Current Transformer
Voltage Transformer
Display
Configuration
ESC
INFORMATION
Before configuring the current transformer ratios,
be certain to connect the transformers in compli-
ance with the specifications on the device rating
plate and the technical data!
11.4 Configuring current transformers
item
Device
and confirm with button 3
Enter
.
·The
Device
item is shown in “blue."
In the
Device
item, choose the basic device and
possibly connected current measuring modules
(up to 10 current measuring modules).
·Confirm the
Basic device
item with button 3
Enter
.
·Use button 5 "
" to go to the setting for the
primary side of the current transformers (current
measurement inputs I1..I4).
Fig. Window Current transformer -> item Device
Device
Transformer 1..4
Transformer 5..8
Main Device
Primary
Secondary
Current Transformer
ESC
5 A
5 A
5 A
5 A
·The item for the primary side of the current trans-
formers I1..I4 is marked in “blue."
·Press button 3
Enter.
·The item for the primary side of the current
transformers I1..I4 “blinks."
·Use buttons 4 (
) and 6 (
) to change the
position of the digit to be set and buttons 2 (
5
)
and 5 (
) to change the digit (-1/+1).
·Confirm your entries with button 3
Enter
or end
the action by pressing button 1
ESC
.
·Use button 6 (
) to go to the configuration of the
secondary side of the current transformers I1..I4.
·Configure the secondary side of the current
transformers I1..I4 in the same way.
·Confirm your entries with button 3
Enter
or end
the action by pressing button 1
ESC
.
·When you have finished entering data, press
button 1
ESC
to return to the
Menu
window.
·For the configuration of the
Current transformer
ratios I5..I8
, press button 5 "
" to go to the
configuration of the primary side of the current
transformers I5..I6.
·Configure the
Current transformer ratios I5..I8
in accordance with the current transformer ratios
I1..I4!
Fig. Window Current transformer -> item Primary
for current transformer 1..4.
5 A
5 A
5 A
5 A
Device
Transformer 1..4
Transformer 5..8
Main Device
Primary
Secondary
Current Transformer
ESC
Содержание UMG 801
Страница 9: ...www janitza de UMG 801 9...
Страница 31: ...www janitza de UMG 801 31...
Страница 47: ...www janitza de UMG 801 47...
Страница 91: ...www janitza de UMG 801 91...
Страница 105: ...www janitza de UMG 801 105...