Page 77
= Key 1
= Key 2
= Key 3
= Maximum or consumption = Minimum or supply
Table 2
Energy in floating point format
Description
Index Address
(dez)
r/w
1)
Type
Unit Comment
DPV1
DPV0/MODB.
Real energy, Consumption 220
2000
r
double[4]
Wh
Energy, Tariff1, Tariff2, Tariff3, Tariff4
Reactive energy, inductive 221
2010
r
double[4]
varh
Energy, Tariff1, Tariff2, Tariff3, Tariff4
Reactive energy, capacitive 222
2020
r
double[4]
varh
Energy, Tariff1, Tariff2, Tariff3, Tariff4
Real energy, supply
223
2030
r
double[4]
Wh
Energy, Tariff1, Tariff2, Tariff3, Tariff4
Reactive energy
without rev. running stop
224
2040
r
double[4]
varh
Energy, Tariff1, Tariff2, Tariff3, Tariff4
Real energy
without rev. running stop
225
2050
r
double[4]
Wh
Energy, Tariff1, Tariff2, Tariff3, Tariff4