Page 85
= Key 1
= Key 2
= Key 3
= Maximum or consumption = Minimum or supply
Table 9
In and outputs
A remote Bit is assigned to each in- or output, that can be controlled externally. If this remote Bit=0, the in- or output
is controlled by the UMG 503 only. If the remote Bit=1, the in- or output is controlled externally.
Description
Address
Format
r/w
1)
Comment
Inputs
0048
word[3]
r/w
Bit 0
Change over summer time (Winter=0, Summer=1)
r/w
Bit 1
Remote, change over summer time
r/w
Bit 2
Relay output 2
r/w
Bit 3
Remote Bit, Relay output 2
r/w
Bit 4
Relay output 1
r/w
Bit 5
Remote Bit, Relay output 1
Bit 6..15
Free
r/w
Bit 0
Remote Bit, Tariffs
r
Bit 1
Synchronize of the internal clock
Bit 2..3
Free
r/w
Bit 4
Reset of real power EMAX
r/w
Bit 5
Remote Bit, Reset of real power EMAX
Bit 6..15
Free
r
Bit 0..1
Tariff real energy consumption
r
Bit 2..3
Tariff reactive energy Ind.
r
Bit 4..5
Tariff reactive energy cap.
Bit 6..15
Free
Outputs
0032
word[3]
r
Bit 0
Measuring range of voltage in L1 exceeded
r
Bit 1
Measuring range of voltage in L2 exceeded
r
Bit 2
Measuring range of voltage in L3 exceeded
r
Bit 3
Measuring range of voltage in L1 underscored
r
Bit 4
Measuring range of voltage in L2 underscored
r
Bit 5
Measuring range of voltage in L3 underscored
Bit 6..15
Free
r
Bit 0
Measuring range of current in L1 exceeded
r
Bit 1
Measuring range of current in L2 exceeded
r
Bit 2
Measuring range of current in L3 exceeded
r
Bit 3
Measuring range of current in L1 underscored
r
Bit 4
Measuring range of current in L2 underscored
r
Bit 5
Measuring range of current in L3 underscored
Bit 6..15
Free
r
Bit 0..2
Watchdogcounter
r
Bit 3
Auxiliary input
Bit 4..15
Free
1)
r/w = read/write