Page 54
= Key 1
= Key 2
= Key 3
= Maximum or consumption = Minimum or supply.
Pulse output (Option)
Corresponding to the mechanical energy meters, the UMG
503 has a pulse output as well. At the pulse output, the
energy of real and reactive energy meters can be given
out. The minimum pulse duration is 50 ms and the maxi-
mum frequency is 10Hz.
If more than one pulse per second is given out by the
pulse output, the pulse gap is not proportional to the
power anymore. If less than one pulse per second is
given out by the pulse output, the pulse gap is proportio-
nal to the power. The inaccuracy of the pulse gap is +-
10ms.
Assign energy
Various measured values can be assigned to the pulse
output of the UMG 503
Without reverse running stop
Consumption
T00, T01, T02, T03, T04
Supply
T00, T01, T02, T03, T04
Reactive energy
Without reverse running stop
inductive (ind)
T00, T01, T02, T03, T04
capacitive (cap)
T00, T01, T02, T03, T04
Pulse valency
Iw=0,000Wh/Pulse
Real energy
Sum
Consumption
Scroll to the indication
of the pulse output in
menu
CONF
with
key
3
.
Wh
L1
L2
L3
CONF
T
Confirm the selection
using
key 1
.
The middle indication
is flashing and the text
EDIT
appears.
Wh
L1
L2
L3
EDIT
CONF
T
Switch to the measured
value selection pressing
key 2
.
T h e p i c t u r e i n t h e
margin appears.
With
key 2
and
key 3
the desired energy can
be assigned to the
pul-
se output
.
M Wh
kWh
Wh
L1
L2
L3
T
Confirm selection
with
key 1
.
The text
EDIT
appears.
With
key 2
change into
the edit mode.
The f irst number is
flashing.
Wh
L1
L2
L3
EDIT
CONF
T
To leave the menu, press
key 1
so often until the text
EDIT
disappears. Pressing
key 3
you switch to the next
menu.
Attention!
When the pulse output is assigned to
real energy
meter without reverse running stop
, pulses are
given out for consumption and supply.
If the pulse output is assigned to the
reactive
energy meter without reverse running stop
,
pulses are given out for inductive and capacitive
load.
If the measured work exceeds the set pulse valency, so
that the maximum for the pulse output is exceeded, the
rest of the pulses are saved and given out later. Up to
32000 pulses are saved in the pulse memory.
Display example for the
pulse output:
Wh
L1
L2
L3
CONF
T
Diagr.: Connection example for pulse output
UMG503