background image

Page 18

POOL PRODUCTS

6.

Set the thermostat to the desired temperature.

Until the pool water reaches a temperature of

approximately 70°F (21°C), there may be

condensate on the heat exchanger. This will stop

after the water reaches the right temperature.
If the heater is installed in an enclosed area, keep

all doors and windows open during the first two hours

of operation. After a long shutdown, there may be

some smoke-like emissions from the heater when it is

first fired. This condition will only last a few minutes.

7.5. Setting the Time Clock

The most economical and trouble-free way of

operating a pool heater and filter system is to include a

time clock in the system for automatic cycling.

Adjust the stops on the time clock to provide a

single filter cycle every 24 hours.

The ON cycle should be at least 12 hours to

allow the filter system to properly clean the pool. Set

the ON cycle at least 4 to 6 hours before the pool is to

be used. During cold spells, the heater may have to be

on longer to maintain the proper pool temperature.

Remove all stops on the time clock during these

periods.

IMPORTANT:

 Run the heater continuously

during the initial warm-up period by removing all time

clock stops. If the pool temperature is going to be

maintained on standby temperature, operate the filter

pump until the water temperature reaches 70°F

(21°C). If the pool is going to be used for swimming,

bring the water up to swimming temperature before

replacing the time clock stops.

When the water reaches the temperature level

on the thermostat, the heater will turn off

automatically, but the filter pump will continue to run

for about 20 minutes.

7.6 Adjusting the Water Pressure Switch

 CAUTION

The water pressure switch should be adjusted to turn

the heater off when the pump is off. Setting the

switch to close at too low of a flow can damage the

appliance. Adjust the switch to turn the heater off,

not on.

The pressure switch is preset at the factory for

activation at 2 psi (14 kPa). However, it is adjustable

in the range of 0.5 psi to 15 psi. Adjust the pressure

switch 

only 

if any part of the filter system piping or

water level of the pool is 3 feet (0.91 m) or more

above or below the top of the heater jacket.

Do not adjust the pressure switch if the heater is

installed more than 15 feet (4.57 m) below or 6 feet

(1.83 m) above the pool surface. Consult your local

Jandy representative for recommendations.

On some installations, the piping from the heater

to the pool is very short. The back pressure could be

too low to trigger the pressure switch. If this happens,

it may be necessary to install a directional fitting or

elbows where the return line enters the pool. This will

increase back pressure enough for the heater to

operate properly.

Make sure the pool filter is clean before making

any pressure switch adjustment: A dirty filter will

restrict the water flow and the pressure switch cannot

be adjusted properly.

To adjust the pressure switch, proceed as

follows:

1.

Set the heater control to the "OFF" position.

2.

Start the filter pump and confirm by means of an

meter that the pressure switch closes. If the

switch fails to close, slowly turn the thumb wheel

on the pressure switch counterclockwise (when

looking at the electrical connections end of the

switch) until the switch closes. If the switch still

fails to close call your Jandy representative or the

Water Pik Technologies Technical  Service

Department at 707.776.8200 extension 260.

3.

Turn the thermostat to the maximum setting and

set the heater control to the 'ON' position. The

heater should start.

4.

Turn the thumb wheel on the pressure switch

very slowly clockwise until the heater goes off.

5.

Slowly turn the pressure switch thumb wheel

counterclockwise

  one-quarter  turn.  The  heater

should come back on.

Figure 18. Initial Air Adjustment.

Содержание DP3000

Страница 1: ...erty damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL FUEL Do not try to light...

Страница 2: ...Sanitizing Chemicals 13 SECTION 6 Electrical 6 1 GeneralInformation 14 6 2 MainPower 14 6 3 Bonding 14 6 4 Auxiliary Time Clock Wiring 14 SECTION 7 Operating Instructions 7 1 NormalOperation 15 7 2 S...

Страница 3: ...cautions are identified by the symbol Be sure to read and comply with all of the warnings and cautions WARNING For your safety do not store gasoline or other flammable liquids or vapors in the vicinit...

Страница 4: ...nstallation date and name of the installer Shipping costs are not included in the warranty coverage The warranty does NOT cover damage caused byimproperassembly installation operationorfield modificat...

Страница 5: ...ee Section 2 3 3 Non combustible bases are available from your Jandy distributor 1 8 Specifications 1 8 1 General Specifications 1 InstallationLocation Certified for use In the USA Indoor and Outdoor...

Страница 6: ...ned Use the two screws supplied in the small envelope to secure the ends together Install the inner stack 7 18cm diameter on the collar of the flue collector before attaching the vent cap outdoor inst...

Страница 7: ...carpet floor without placing a noncombustible platform between the floor and the heater The heater can be installed on a combustible floor if a noncombustible base assembly available from Jandy is us...

Страница 8: ...pen on three sides This prevents combustion gases from being diverted into living areas through doors windows or gravity inlets If the heater is installed close to a structure protect it from rain wat...

Страница 9: ...ough horizontal ducts each opening and duct must provide one square inch of flow area for each 2000 BTU Hr 0 6 kW The XL 3 model DP3000 has an input rating of 315 000 BTU Hr The vent opening requireme...

Страница 10: ...ble provisions of the local buildingcodes 2 In Canada CAN CGA B149 1 or 2 Avoid terminating heater vents near air conditioning or air supply fans The fans can pick up exhaust flue products from the he...

Страница 11: ...l oil or 2 diesel fuel will be used to supply the heater Laars XL 3 heaters as shipped from the factory are certified to operate at sea level but the burner air shutter can be adjusted to operate the...

Страница 12: ...the heater water connections are no more than six feet below the pool water surface and no more than 15 feet above it See instructions for pressure switch adjustment Section 7 6 for more information...

Страница 13: ...heat exchanger on a previously installed heater be sure that all electrical power the gas supply and water supply have been turned off before starting the procedure Follow these step by step instructi...

Страница 14: ...2 Replace the top assembly and fasten it in place with the eight screws 2 previously removed Install the inner stack 23 Reinstall the inner stack 1 Install the chimney cap assembly or barometric draft...

Страница 15: ...ectly to the inlet outlet header by threading it into the hole 3 Route the discharge piping so that steam from the pipe does not endanger anyone near the heater Refer to your local installation codes...

Страница 16: ...CAUTION This heater must be connected to a bonding grid with a solid copper wire not smaller in diameter than 8 ga The National Electrical Code and most other codes require that all metallic componen...

Страница 17: ...essure in the piping the contacts in the heater pressure switch close Figure 14 Wiring Diagram 60 Hz Model 2 The heater thermostat calls for heat completing the circuit between the two thermostat term...

Страница 18: ...he firebox during shipping At initial start up and at start up after a prolonged period of non use inspect the firebox for damage or deterioration Remove the cover plate and plug from the inspection h...

Страница 19: ...r Make sure of the proper air adjustment The air shutter is factory set for 12 C02 but verify this after installation When starting the heater follow these steps 1 Start the filter pump Let it run for...

Страница 20: ...o close at too low of a flow can damage the appliance Adjust the switch to turn the heater off not on The pressure switch is preset at the factory for activation at 2 psi 14 kPa However it is adjustab...

Страница 21: ...nstall the special thread adapter and Pete s plug fitting and insert a pocket thermometer A temperature rise measurement kit is available through your Jandy distributor See section 10 of this manual f...

Страница 22: ...ed Level Free Chlorine or 1 0 to 3 0 ppm Bromine 3 0 to 5 0 ppm pH 7 2 to 7 6 Total Alkalinity TA 80 to 120 ppm Calcium Hardness CH 200 to 400 ppm Langelier Saturation Index SI 0 5 to 0 5 Cyanuric Aci...

Страница 23: ...a circuit breaker was switched off during the winter be sure that the breaker is back on 6 Turn on the heater following the start up instruc tions in this manual see Section 7 2 8 3 Inspection and Se...

Страница 24: ...e as necessary 12 Clean the heat exchanger using the following schedule After installation and first start up check the heat exchanger for black carbon soot buildup after the following periods of oper...

Страница 25: ...eater switch OFF and call a service technician 9 2 Professional Troubleshooting Guide 9 2 1Introduction A qualified oil burner technician must service this equipment Frequently this service is availab...

Страница 26: ...caused by Foulednozzle Fuel line air leaks Improper nozzle pressure pressure should be 100 psi Improper air setting see Section 9 2 3 4 4 Press the reset button on the motor If the unit does not star...

Страница 27: ...Off Remove one of the thermostat leads from the primary control If the oil burner shuts off the problem is in the heater control circuit The circuit includes the pressure switch high limit safety swi...

Страница 28: ...ness 135 f All R0057700 16 High Limit Switch Cover with Gasket All R0390400 17 ON OFF Switch with Cover and Gask All R0390500 19 Gasket Only All R0390600 20 Oil Burner Harness All R0057600 21 Connecto...

Страница 29: ...PARTS COMPONENTS Not Shown 61 End Air Shutter All R0387800 62 Bulk Air Band All R0387900 63 Tube Gasket All R0388000 64 Motor 1 7 H P 3450 RPM All R0388100 65 Blower Wheel 4 1 4 x 3 7 16 All R0388200...

Страница 30: ...UCTS 46 1 44 45 60 59 27 23 42 32 9 10 17 8 4 28 33 30 23 27 35 34 26 25 52 51 53 54 55 56 57 7 5 7 6 14 80 25 15 37 38 40 13 16 29 22 14 21 41 43 7 2 3 12 19 20 29 30 33 34 35 36 47 48 49 50 58 81 10...

Страница 31: ...Model DP Oil Fired Heater Page 29 NOTES...

Страница 32: ...ow rates outside the published minimum and maximum specifications 7 Use of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or i...

Отзывы: