Page 6

POOL PRODUCTS

2.3.4 Outdoor Installation

For outdoor configuration, the XL-3 heater must

be installed with a factory authorized vent cap installed

over the inner stack. See Section 2.2, "Field Assembly"

for installation of the inner stack. See Section 10,

"Parts List" for instructions on ordering a factory

authorized vent cap.

Locate the heater in an 

open, unroofed area

.

Do not install the heater under a deck. Do not locate

the heater below or adjacent to any doors, glass

openings, louvers, grills, etc., which connect in any

way with an inhabited area of a building, even though

the access might be through another structure (e.g., a

garage or utility room). In the United States there must

be a minimum of four (4) feet (1.22 m) horizontally

and 

four (4) feet (1.22 m) vertically between the

heater exhaust point and any door, glass opening, or

gravity inlet to a building. In Canada, the heater must

be installed so that the exhaust point of the heater is at

least ten (10) feet (3.0 m) from any building opening

(see Figure 4).

 WARNING

United States

Do not install the heater with the top of the vent

assembly within 4 feet (1.22 m) horizontally and 4

feet (1.22 m) vertically of any opening into a building.

Canada

Do not install the heater with the top of the vent

assembly within 10 feet (3.05 m) of any opening into

a building.

The top surface of the heater must be at least

three (3) feet above any forced air inlet, or intake

ducts located within ten (10) feet horizontally.

If the heater is installed under an overhang, there

must be a minimum clearance of 5 feet (1.5 m) above

the top of the heater and the structure should not

overhang the heater more than 12 inches (0.30 m). The

area under the overhang must be open on three sides.

This prevents combustion gases from being diverted

into living areas through doors, windows, or gravity

inlets.

If the heater is installed close to a structure,

protect it from rain water runoff with rain gutters on

the roof or other measures. Do not locate the heater

near irrigation sprinkler systems that could spray water

on it. Water from sprinklers may cause damage to

controls and electronic components.

Avoid locations where wind deflection off nearby

structures might cause downdraft conditions. Where

downdraft conditions exist, locate the heater at least 3

feet (0.91 m) from vertical surfaces (e.g., nearby

buildings and walls).

2.3.5 Indoor and Outdoor Shelter

Installations

An outdoor shelter (Canada only) is an

unoccupied enclosure which does not communicate

directly with occupied areas. All indoor installations

and outdoor shelter installations require the addition of

a factory approved barometric draft control. The

barometric draft control must be installed without

modification and in accordance with the instructions

provided by the manufacturer.

These codes, standards and Water Pik

Technologies require that the heater be properly

vented as outlined in this manual. Proper ventilation of

exhaust and combustion air are essential for the safe

and efficient operation of the heater (See Section 3

"Venting").

2.3.5.1 Installing a Barometric Draft

Control

A barometric draft control must be installed

between the heater and the vent pipe with a minimum

13 inch clearance between the chimney connector and

any combustible material. Observe NFPA Standard

No. 31 and all national and local ordinances. See

Section 3 "Venting" for the proper location of the

barometric draft control when constructing the stack.

For more information on the correct barometric draft

control for your heater, contact your local Jandy Pool

Products dealer.

Figure 4.  Outdoor Heater Installation.

Содержание DP3000

Страница 1: ...erty damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL FUEL Do not try to light...

Страница 2: ...Sanitizing Chemicals 13 SECTION 6 Electrical 6 1 GeneralInformation 14 6 2 MainPower 14 6 3 Bonding 14 6 4 Auxiliary Time Clock Wiring 14 SECTION 7 Operating Instructions 7 1 NormalOperation 15 7 2 S...

Страница 3: ...cautions are identified by the symbol Be sure to read and comply with all of the warnings and cautions WARNING For your safety do not store gasoline or other flammable liquids or vapors in the vicinit...

Страница 4: ...nstallation date and name of the installer Shipping costs are not included in the warranty coverage The warranty does NOT cover damage caused byimproperassembly installation operationorfield modificat...

Страница 5: ...ee Section 2 3 3 Non combustible bases are available from your Jandy distributor 1 8 Specifications 1 8 1 General Specifications 1 InstallationLocation Certified for use In the USA Indoor and Outdoor...

Страница 6: ...ned Use the two screws supplied in the small envelope to secure the ends together Install the inner stack 7 18cm diameter on the collar of the flue collector before attaching the vent cap outdoor inst...

Страница 7: ...carpet floor without placing a noncombustible platform between the floor and the heater The heater can be installed on a combustible floor if a noncombustible base assembly available from Jandy is us...

Страница 8: ...pen on three sides This prevents combustion gases from being diverted into living areas through doors windows or gravity inlets If the heater is installed close to a structure protect it from rain wat...

Страница 9: ...ough horizontal ducts each opening and duct must provide one square inch of flow area for each 2000 BTU Hr 0 6 kW The XL 3 model DP3000 has an input rating of 315 000 BTU Hr The vent opening requireme...

Страница 10: ...ble provisions of the local buildingcodes 2 In Canada CAN CGA B149 1 or 2 Avoid terminating heater vents near air conditioning or air supply fans The fans can pick up exhaust flue products from the he...

Страница 11: ...l oil or 2 diesel fuel will be used to supply the heater Laars XL 3 heaters as shipped from the factory are certified to operate at sea level but the burner air shutter can be adjusted to operate the...

Страница 12: ...the heater water connections are no more than six feet below the pool water surface and no more than 15 feet above it See instructions for pressure switch adjustment Section 7 6 for more information...

Страница 13: ...heat exchanger on a previously installed heater be sure that all electrical power the gas supply and water supply have been turned off before starting the procedure Follow these step by step instructi...

Страница 14: ...2 Replace the top assembly and fasten it in place with the eight screws 2 previously removed Install the inner stack 23 Reinstall the inner stack 1 Install the chimney cap assembly or barometric draft...

Страница 15: ...ectly to the inlet outlet header by threading it into the hole 3 Route the discharge piping so that steam from the pipe does not endanger anyone near the heater Refer to your local installation codes...

Страница 16: ...CAUTION This heater must be connected to a bonding grid with a solid copper wire not smaller in diameter than 8 ga The National Electrical Code and most other codes require that all metallic componen...

Страница 17: ...essure in the piping the contacts in the heater pressure switch close Figure 14 Wiring Diagram 60 Hz Model 2 The heater thermostat calls for heat completing the circuit between the two thermostat term...

Страница 18: ...he firebox during shipping At initial start up and at start up after a prolonged period of non use inspect the firebox for damage or deterioration Remove the cover plate and plug from the inspection h...

Страница 19: ...r Make sure of the proper air adjustment The air shutter is factory set for 12 C02 but verify this after installation When starting the heater follow these steps 1 Start the filter pump Let it run for...

Страница 20: ...o close at too low of a flow can damage the appliance Adjust the switch to turn the heater off not on The pressure switch is preset at the factory for activation at 2 psi 14 kPa However it is adjustab...

Страница 21: ...nstall the special thread adapter and Pete s plug fitting and insert a pocket thermometer A temperature rise measurement kit is available through your Jandy distributor See section 10 of this manual f...

Страница 22: ...ed Level Free Chlorine or 1 0 to 3 0 ppm Bromine 3 0 to 5 0 ppm pH 7 2 to 7 6 Total Alkalinity TA 80 to 120 ppm Calcium Hardness CH 200 to 400 ppm Langelier Saturation Index SI 0 5 to 0 5 Cyanuric Aci...

Страница 23: ...a circuit breaker was switched off during the winter be sure that the breaker is back on 6 Turn on the heater following the start up instruc tions in this manual see Section 7 2 8 3 Inspection and Se...

Страница 24: ...e as necessary 12 Clean the heat exchanger using the following schedule After installation and first start up check the heat exchanger for black carbon soot buildup after the following periods of oper...

Страница 25: ...eater switch OFF and call a service technician 9 2 Professional Troubleshooting Guide 9 2 1Introduction A qualified oil burner technician must service this equipment Frequently this service is availab...

Страница 26: ...caused by Foulednozzle Fuel line air leaks Improper nozzle pressure pressure should be 100 psi Improper air setting see Section 9 2 3 4 4 Press the reset button on the motor If the unit does not star...

Страница 27: ...Off Remove one of the thermostat leads from the primary control If the oil burner shuts off the problem is in the heater control circuit The circuit includes the pressure switch high limit safety swi...

Страница 28: ...ness 135 f All R0057700 16 High Limit Switch Cover with Gasket All R0390400 17 ON OFF Switch with Cover and Gask All R0390500 19 Gasket Only All R0390600 20 Oil Burner Harness All R0057600 21 Connecto...

Страница 29: ...PARTS COMPONENTS Not Shown 61 End Air Shutter All R0387800 62 Bulk Air Band All R0387900 63 Tube Gasket All R0388000 64 Motor 1 7 H P 3450 RPM All R0388100 65 Blower Wheel 4 1 4 x 3 7 16 All R0388200...

Страница 30: ...UCTS 46 1 44 45 60 59 27 23 42 32 9 10 17 8 4 28 33 30 23 27 35 34 26 25 52 51 53 54 55 56 57 7 5 7 6 14 80 25 15 37 38 40 13 16 29 22 14 21 41 43 7 2 3 12 19 20 29 30 33 34 35 36 47 48 49 50 58 81 10...

Страница 31: ...Model DP Oil Fired Heater Page 29 NOTES...

Страница 32: ...ow rates outside the published minimum and maximum specifications 7 Use of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or i...

Отзывы: