4.3  DIP Switch Settings for Pool or Spa Only

S1 DIP Switch #

OFF

ON

1

AUX1= any equipment

AUX1= Pool Cleaner

2

AUX2= any equipment

AUX2= Low Speed for a two-speed filter pump.

Filter pump circuit becomes High Speed.

3

AUX3= any equipment

No change

4

Heater cool down operates.

Heater cool down disabled.

5

Normal operation

Factory adjustment- when this switch is on, 

temperature delays are eliminated and solar 

temperature is displayed.  

Do not leave this switch in the ON position.

6

Spare

No change

7

Spare

No change

8

After thermostat setting has been reached, 

heater will remain OFF for 3 minutes.

Heat Pump installed; after thermostat setting 

has been reached, heater will remain OFF for 5 

minutes.

S2 DIP Switch #

OFF

ON

1

The AquaLink RS will be able to control a 

Solar Heating system (If a solar sensor is 

connected to the solar sensor input).

The AquaLink RS will be able to control a Heat 

Pump. (The AquaLink RS will not be able to 

control a Solar Heating system.)

2

NOT USED

3

NOT USED

4

NOT USED

4.4  DIP Switch Settings for heat Pump Installation

This table shows how to configure the system for SOLAR PRIORITY or HEAT PUMP PRIORITY.

DIP S2-1

GREEN 10-PIN 

TERMINAL BAR

RS485 hEAT PUMP

DESCRIPTION

OFF

No sensor installed

Not connected

In this configuration there is no Solar Heating and no 

Heat Pump. Extra AUX is available.

OFF

Sensor installed

Not connected

In this configuration there is Solar Heating and there 

is Solar Priority. There is no Heat Pump.

OFF

Sensor installed

Connected

In this configuration there is Solar Heating and there 

is Solar Priority. There is Heat Pump. There is Heat 

Pump Priority.

ON

No sensor installed

Not connected

In this configuration there is no Solar Heating. There 

is a mechanically connected Heat Pump. There is 

Heat Pump Priority (a limited implementation).

ON

Sensor installed

Not connected

In this configuration there is no Solar Heating. There 

is a mechanically connected Heat Pump. There is 

Heat Pump Priority (full implementation).

ON

Sensor installed

Connected

In this configuration there is no Solar Heating. There 

is an RS485 controlled Heat Pump. There is Heat 

Pump Priority.

Содержание AquaLink RS6

Страница 1: ...product must be installed and serviced by a professional pool spa service technician The procedures in this manual must be followed exactly Failure to follow warning notices and instructions may resul...

Страница 2: ......

Страница 3: ...nnecting Equipment to PCB 10 3 6 Setting DIP Switches 10 3 7 Installing Power Center Faceplate 10 Section 4 Power Center PCB DIP Switch Settings 11 4 1 DIP Switch Functions 11 4 2 DIP Switch Settings...

Страница 4: ...regnant or possibly pregnant women should limit spa water temperatures to 100 F 38 C c Before entering a spa or hot tub the user should measure the water temperature with an accurate thermometer since...

Страница 5: ...ure the water temperature with an accurate thermometer Do not use a spa or hot tub immediately following strenuous exercise Prolonged immersion in a spa or hot tub may be injurious to your health Do n...

Страница 6: ...ional Relays when necessary OneTouch Control Panel Power Center PCB Three 3 Temp Sensors Additional Relays when necessary Standard Power Center with mounting brackets 4 3 HP Relays and RS Transformer...

Страница 7: ...age Class 2 1 A 24 VAC Emergency Service Switch All Circuits located at Power Center in Service Mode Dimensions 8 All Button Control Panel One TouchTM Control Panel Wireless Control Panel 14 1 2 3 4 5...

Страница 8: ...ol Intake Spa Intake Spa Return Pool Return Pool Filter Spa Filter Check Valve optional Check Valve Optional NOTE When connecting to the AquaLink RS plug the JVAs into the Intake Return and Cleaner JV...

Страница 9: ...rground or in concrete it must be run in conduit Never run high voltage and low voltage cables in the same conduit 2 Pull the Control Panel Cable into the low voltage compartment 3 Strip back cable ja...

Страница 10: ...uipment to PCB Connect the high voltage relay plugs into their appropriate sockets according to the wiring diagram located on the inside of the Power Center door see Section 5 Figure 5 NOTE Pool filte...

Страница 11: ...Valve Actuator does not rotate the spa will fill with water and overflow into the pool Note Leave AUX 3 relay socket empty CAUTION Turn this DIP Switch ON only if you are using an electric heater or a...

Страница 12: ...olar sensor Air temperature no longer displayed Adjustable Freese Kit must be added for freeze protection 8 After thermostat setting has been reached heater will remain OFF for 3 minutes Heat Pump ins...

Страница 13: ...ystem 2 NOT USED 3 NOT USED 4 NOT USED 4 4 DIP Switch Settings for Heat Pump Installation This table shows how to configure the system for SOLAR PRIORITY or HEAT PUMP PRIORITY DIP S2 1 GREEN 10 PIN TE...

Страница 14: ...o Sensors etc green terminal bar To Remote brown terminal bar To Controller red terminal bar F P u m p A u x 1 A u x 2 A u x 3 Relay Sockets 24 VDC output A u x 4 A u x 5 A u x 6 S p a P u m p C l e a...

Страница 15: ...Page 15 NOTES...

Страница 16: ...ns causing inadequate water circulation 6 Operating the product s at water flow rates outside the published minimum and maximum specifications 7 Use of non factory authorized parts or accessories in c...

Отзывы: