Pro II: Digital-I/O Modules
Pro II-OPT-32-24V Rev. E
ADwin
126
ADwin-Pro II
Hardware, manual Dec. 2018
5.7.7 Pro II-OPT-32-24V Rev. E
The input module Pro II-OPT-32-24V Rev. E provides 32 channels of optically
isolated digital inputs.
The input voltage range is fixed to 24V, which is also true for the event input.
The switching time of only 100ns allows the sampling of high-speed digital
inputs.
The module can automatically monitor the edges of input channels, which is
performed with a frequency of 100MHz. With every change, the current input
levels are saved together with a time stamp in a FIFO; up to 511 of those value
pairs (input level and time stamp) can be stored. The FIFO data can be read
and processed.
In addition, one can query whether a positive or negative edge has occurred
at the input channels.
Each channel is optically isolated from the system circuitry and from the other
inputs. The event-input is optically isolated from the system as well.
The channels are single ended and share the same ground potential (ext.
GND), which has to be provided on the D-Sub connector.
Fig. 108 – Pro II-OPT-32-24V Rev. E: Block diagram
Fig. 109 – Pro II-OPT-32-24V Rev. E: Pin assignment and front panel
ADwin-Pro
II
bus
.....
..........
0
31
Data
Register Data
EVENT
..........
Ext. GND
EXT GND
reserviert
EXT GND
OPT IN 30
OPT IN 28
OPT IN 26
OPT IN 24
OPT IN 22
OPT IN 20
OPT IN 18
OPT IN 16
OPT IN 14
OPT IN 12
OPT IN 10
OPT IN 8
OPT IN 6
OPT IN 4
OPT IN 2
OPT IN 0
EVENT IN
EXT GND
OPT IN 31
OPT IN 29
OPT IN 27
OPT IN 25
OPT IN 23
OPT IN 21
OPT IN 19
OPT IN 17
OPT IN 15
OPT IN 13
OPT IN 11
OPT IN 9
OPT IN 7
OPT IN 5
OPT IN 3
OPT IN 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
OPT32
OPTOCOUPLE
INPUT