Table 4 - Status Indicator Priority Levels
Priority Level
LED
Behavior
Indication / Cause
Priority 1
5x Red
Battery Voltage is Out of Range:
Vbat <
Analog Battery Monitor Lower Limit
(11.4V) or
Vbat >
Analog Battery Monitor Upper Limit
(17.5V)
Priority 2
1X Red
AntiJam Mode has been activated:
Motor Current >
AntiJam A Trigger Current
(4.5A) or
Motor Controller Error has been received.
Priority 3
2X Red
36V Supply is Out of Range:
36V supply <
Analog 36V Monitor Lower Limit
(33.0V) or
36V supply >
Analog 36V Monitor Upper Limit
(39.0V).
If the Charge Controller has the Auxiliary Output turned off, this error is
not displayed.
Priority 4
3X Red
Motor Controller not communicating properly.
If the Charge Controller has the Auxiliary Output turned off, this error is
not displayed.
Priority 5
4X Red
Charge Controller not communication properly.
Priority 6
1X Yellow
Motor Current >
Visual Motor Current Threshold
(3.5A)
Priority 7
2X Yellow
Vbat <
Visual Low Battery Threshold
(12.1V)
Priority 8
3X Yellow
Temperature Reading is Out of Range:
Temp <
Analog Temperature Monitor Lower Limit
(0°F) or
Temp >
Analog Temperature Monitor Upper Limit
(176°F)
Priority 9
4X Yellow
5V Supply is Out of Range:
5V supply <
Analog 5V Monitor Lower Limit
(4.5V) or
5V supply <
Analog 5V Monitor Upper Limit
(5.5V)
Priority 10
5X Yellow
GPS Unit not communicating properly
©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]
SolarBee SCADA
Visual Status Indicator Priority Levels
Register Address 9 (Base 10)
2076_10325_20220110
O&M_SB5000PW_10272_20220119 - 62