BEHAVIOR
VISUAL
INDICATION
BLINK GR
HEALTHY SYSTEM
SOLID R, Y, GR
HARDWARE ERROR
R, Y, GR OFF
HARDWARE ERROR
SOLID BL
SD CARD INSERTED
1X R, Y, GR
CUSTOM SYSTEM
BOOT UP
1X R
ANTI-JAM ROUTINE
2X R
36 VDC OUT OF RANGE
3X R
MOTOR COMM ERROR
4X R
CHARGE COMM ERROR
5X R
BATT OUT OF RANGE
1X Y
HIGH MOTOR CURRENT
2X Y
LOW BATT VOLTAGE
3X Y
TEMP OUT OF RANGE
4X Y
5 VDC OUT OF RANGE
5X Y
GPS COMM ERROR
10X R, Y, GR
INCOMPLETE SD
CARD UPDATE
1X Y, GR
GPS SATELLITE
LOCK ERROR
DB9 Connector
(SCADA)
SD Card
Slot
GR
GR
5 Amp Fuse
(Grid-Boost
Option Only)
Power Relay
(Grid-Boost
Option Only)
R
R
Y
Y
BL
MCC
RS-485
Zahn
Board
7.5 Amp
Fuse
36 VDC 12 VDC
20 Amp
Fuse
GR
LED
{
{
- +
+ -
{
+
+ -
12VDC Bat Volt
Brain
Board SN
36VDC Mot Volt
Power Up and Power Down Sequence
Power Down
Component
Power Up
1
On/Off Switch
6
2
PV Panels
5
3
Grid Power (Grid-Boost)
4
4
Battery
3
5
Motor Control Cord (MCC)
2
6
Motor
1
Zahn Board Green LED
On
12 VDC to Zahn
Off No Power to Zahn
MCC
Battery
PV Panel
MCC Connection
Battery Connection
PV Panel
Connections
Grid-Boost Option
(36 VDC connection on right side)
On/Off Switch
Motor
©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]
Troubleshooting
SB Series Status Codes
SB Series: Control Box Lid Label
10575_20220110
O&M_SB5000PW_10272_20220119 - 46