Check for proper operation of all of the limit and 
operating controls, before leaving the site.

AA

G

CC

BB

g.

If you believe the probe to be grounded, follow the 
following steps for a control (G) with a test switch (AA):

1.

Make sure that the liquid level is below the probe.

2.

Depress the test switch (AA). If the amber LED 
(BB) turns "ON" the probe may be grounded. If so, 
replace the grounded probe.

b. Now fill the boiler with water.

For Series PS-801 (auto reset units only)
1.

When water touches the probe, the Red light will start flashing for 15-seconds Delay on Make (DOM) 

and then turn "OFF".

2.

The burner will turn "ON" as long as there is water on the probe.

3.

If a water feeder has been installed it will turn "OFF".

For Series PS-801-M (manual reset units only)

(When water returns to the probe, nothing will happen until the manual reset button is depressed.)

1.

After depressing manual reset button, the Green and Red lights will flash simultaneously 4 times.

2.

Then the Green light will turn "ON".

3.

The Red light will continue to flash for 15-seconds (DOM) and then turn "OFF".

4.

The burner will turn "ON" as long as there is water on the probe.

(

Warning: To prevent flooding, never use a “water feeder” with a manual reset low water cut-off.)

c. Slowly drain the boiler of water.

For all Series PS-801 (both auto and manual reset units)

1.

When water drops off the probe, the Red light will start flashing for 10-seconds (DOB) and then 

turn "ON".

2.

The burner will turn "OFF".

3.

If a water feeder has been installed and does not have a time delay, it should turn "ON".

(Warning: To prevent flooding, never use a “water feeder” with a manual reset low water cut-off.)

Manually Testing  Control

For Series PS-801 & PS-801-M with Red (Low Water) and Green (Power) Lights

a. Before filling the system

, turn on the electric power to the boiler. Set the thermostat to "heat".

For all Series PS-801
1.

Upon initial power up, the Green and Red lights will flash simultaneously 4 times.

2.

The Green light will turn "ON".

3.

The Red light will continue to flash for 10-seconds Delay on Break (DOB) and then turn "ON".

4

. If a water feeder has been installed and does not have a time delay, it will turn "ON".

5.

The burner will never turn "ON" during power up, if water is off the probe.

Start-Up

Содержание McDonnell & Miller GuardDog PS-801 Series

Страница 1: ...for proper operation of all of the limit and operating controls before leaving the site We recommend that secondary redundant Low Water Cut Off controls be installed on all steam boilers with heat in...

Страница 2: ...st lights 3 000 ohm For models with red low water and green power lights 7 000 ohm Control Power Consumption For models with red low water and amber test lights 3 VA For models with red low water and...

Страница 3: ...ine suitable tapping for the probe 2 Locate probe in supply piping using a tee fitting STEP 1 Locating and Installing the Probe 3 1 4 6mm 1 4 6mm A E A F c Using a wrench tighten the probe A into the...

Страница 4: ...clockwise so that the slots in the control base are firmly under the screw heads Tighten the mounting screws F to approximately 2 ft lb 2 6 N m d Identify a desirable location to mount the control as...

Страница 5: ...l shock turn off the electrical power before making electrical connections This low water cut off must be installed in series with all other limit and operating controls installed on the boiler After...

Страница 6: ...ing of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C Failure to follow this warning could cause property damage personal injury or death WARNING Models with Red low water and Amber test Li...

Страница 7: ...CUIT C B D A N 120 VOLT CIRCUIT Connect Hot wire A of 120 volt circuit to terminal H Connect Neutral wire B of 120 volt circuit to terminal N Connect wire C from beginning of Burner circuit thermostat...

Страница 8: ...r LED BB on top of the control housing G 1 If the amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pu...

Страница 9: ...ntinue to flash for 15 seconds DOM and then turn OFF 4 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low water...

Страница 10: ...light will flash for 15 seconds DOB and then turn OFF 7 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low wate...

Страница 11: ...turn ON as long as there is water on the probe Testing Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button to activate test...

Страница 12: ...e adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAUTION C...

Отзывы: