background image

A

D

a.

Based on the following criteria locate a suitable position for the probe (A):

b.

Sparingly, apply pipe sealant to the external
threads (D) of the probe (A).

For all Applications:

1. Make sure probe is installed above minimum 

safe water line as determined by the boiler 
manufacturer.

2. Make sure that ends and sides of the probe 

are at least 1/4” (6.4mm) from all internal 
metal surfaces.

3. Make sure the probe is positioned to shut off 

the boiler before the water level falls below 
the lowest visible part of the gauge glass.

For Steam Boilers:

1. Refer to boiler manufacturers instructions to 

determine suitable tapping for the probe.

For Hot Water Boilers:

1. Refer to boiler manufacturers instructions to 

determine suitable tapping for the probe.

2. Locate probe in supply piping using a tee fitting.

STEP 1 - Locating and Installing the Probe

3

1/4"

(6mm)

1/4" (6mm)

A

E

A

F

c.

Using a wrench, tighten the probe (A) into the
tapped connection (E) that was determined in Step
1 of these instructions. Tighten to 47 ft•lb (64 N•m).
NOTE: Be sure to align the probe so that the
mounting screws (F) are in a horizontal position.

IMPORTANT:

Do not use Teflon® tape. Only use

pipe sealant.

Probe

Control

Riser

Pipe

Hot Water

Boiler

Tee Fitting

Probe

Control

Minimum Safe

Water Level

(May vary 

by boiler 

manufacturer)

Steam or

Hot Water

Boiler

INSTALLATION

TOOLS NEEDED:

One (1) flathead screwdriver, and one (1) pipe wrench.
For Remote Installations a level and power drill will be required.

STEP 2 - Installing Control Box

G

a.

Using a flathead screwdriver, loosen the two (2) screws
that secure the cover (G) to the control about 1-1/2
turns and remove cover.

Содержание McDonnell & Miller GuardDog PS-801 Series

Страница 1: ...for proper operation of all of the limit and operating controls before leaving the site We recommend that secondary redundant Low Water Cut Off controls be installed on all steam boilers with heat in...

Страница 2: ...st lights 3 000 ohm For models with red low water and green power lights 7 000 ohm Control Power Consumption For models with red low water and amber test lights 3 VA For models with red low water and...

Страница 3: ...ine suitable tapping for the probe 2 Locate probe in supply piping using a tee fitting STEP 1 Locating and Installing the Probe 3 1 4 6mm 1 4 6mm A E A F c Using a wrench tighten the probe A into the...

Страница 4: ...clockwise so that the slots in the control base are firmly under the screw heads Tighten the mounting screws F to approximately 2 ft lb 2 6 N m d Identify a desirable location to mount the control as...

Страница 5: ...l shock turn off the electrical power before making electrical connections This low water cut off must be installed in series with all other limit and operating controls installed on the boiler After...

Страница 6: ...ing of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C Failure to follow this warning could cause property damage personal injury or death WARNING Models with Red low water and Amber test Li...

Страница 7: ...CUIT C B D A N 120 VOLT CIRCUIT Connect Hot wire A of 120 volt circuit to terminal H Connect Neutral wire B of 120 volt circuit to terminal N Connect wire C from beginning of Burner circuit thermostat...

Страница 8: ...r LED BB on top of the control housing G 1 If the amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pu...

Страница 9: ...ntinue to flash for 15 seconds DOM and then turn OFF 4 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low water...

Страница 10: ...light will flash for 15 seconds DOB and then turn OFF 7 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low wate...

Страница 11: ...turn ON as long as there is water on the probe Testing Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button to activate test...

Страница 12: ...e adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAUTION C...