6

STEP 4 - Control Wiring (continued)

E

H

1

2

3

4

5

BURNER

CIRCUIT

C

D

B

A

N

120 VOLT

CIRCUIT

• Hot wire (A) of 120 volt circuit to terminal (1).
• Connect Neutral wire (B) of 120 volt circuit to terminal (2).
• Connect wire (C) from beginning of Burner circuit

(thermostat, gas valve, limits, etc.) to terminal (5).

• Connect wire (D) from end of Burner circuit to terminal (2).
• Install wire (E) connecting (1) and (3).

c.

Based on the Boiler’s Control Circuit voltage and the required input voltage of the LWCO, select proper wiring 

diagram and proceed to that page.

Boiler manufacturer schematics should always be
followed. In the event that the boiler manufacturer’s
schematic does not exist, or is not available from
the boiler manufacturer, refer to the schematics
provided in this document.

!

IMPORTANT

To prevent an electrical fire or equipment damage,
electrical wiring must have a rating of 167˚F (75˚C) if the 
liquid's temperature exceeds 180˚F (82˚C).
Failure to follow this warning could cause property 
damage, personal injury or death.

!

WARNING

Models with Red (low water) and Amber (test) Lights

Models with Red (low water) and Green (power) Lights

LWCO Model

Boiler Circuit Voltage

Page

LWCO Model

Boiler Circuit Voltage

Page

PS-801-120

120V

7

PS-801-120

120V

8

PS-801-120

24V

7

PS-801-120

24V

8

PS-851-120

120V

7

PS-851-120

120V

8

PS-851-120

24V

7

PS-851-120

24V

8

N

P

M

d.

For all wire connections to the terminal block (M).

1. Strip about 1/3" (8.5 mm) of insulation from the wire.
2. Loosen the terminal screw (N) but DO NOT 

REMOVE. Move the wire clamping plate (P) back until the 
plate touches the back side of the screw head.

3. Insert the stripped end of the wire under the wire clamping     

plate (P) and securely tighten the terminal screw (N).

Wiring Diagram Legends

1. Bold lines indicate action to be taken in Step shown.
2. Dotted black lines indicate internal wiring.

PS-801/851 with 120 Volt Burner Circuit with Red (Low Water) and
Amber (Test) Lights

Содержание McDonnell & Miller GuardDog PS-801 Series

Страница 1: ...for proper operation of all of the limit and operating controls before leaving the site We recommend that secondary redundant Low Water Cut Off controls be installed on all steam boilers with heat in...

Страница 2: ...st lights 3 000 ohm For models with red low water and green power lights 7 000 ohm Control Power Consumption For models with red low water and amber test lights 3 VA For models with red low water and...

Страница 3: ...ine suitable tapping for the probe 2 Locate probe in supply piping using a tee fitting STEP 1 Locating and Installing the Probe 3 1 4 6mm 1 4 6mm A E A F c Using a wrench tighten the probe A into the...

Страница 4: ...clockwise so that the slots in the control base are firmly under the screw heads Tighten the mounting screws F to approximately 2 ft lb 2 6 N m d Identify a desirable location to mount the control as...

Страница 5: ...l shock turn off the electrical power before making electrical connections This low water cut off must be installed in series with all other limit and operating controls installed on the boiler After...

Страница 6: ...ing of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C Failure to follow this warning could cause property damage personal injury or death WARNING Models with Red low water and Amber test Li...

Страница 7: ...CUIT C B D A N 120 VOLT CIRCUIT Connect Hot wire A of 120 volt circuit to terminal H Connect Neutral wire B of 120 volt circuit to terminal N Connect wire C from beginning of Burner circuit thermostat...

Страница 8: ...r LED BB on top of the control housing G 1 If the amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pu...

Страница 9: ...ntinue to flash for 15 seconds DOM and then turn OFF 4 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low water...

Страница 10: ...light will flash for 15 seconds DOB and then turn OFF 7 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low wate...

Страница 11: ...turn ON as long as there is water on the probe Testing Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button to activate test...

Страница 12: ...e adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAUTION C...

Отзывы: