2

SPECIFICATIONS

Electrical Ratings

Series PS-801 for Steam Boilers

Preset time delays prevent nuisance burner cycling:

15 second Delay on Make (DOM)

10 second Delay on Break (DOB)

Conductive liquid required
(water/glycol mixtures up to 50% concentration may
be used)

Automatic reset after power outage

Maximum Pressure:

15 psi (1kg/cm

2

)

All models include a provision for adding an alarm or
automatic water feeder.

Series PS-851 for Hot Water Boilers

No time delays provided

Conductive liquid required
(water/glycol mixtures up to 50% concentration
may be used)

Automatic reset after power outage

Maximum Water Pressure:

160 psi (11.2kg/cm

2

)

Maximum Water Temperature:

250˚F (121˚C).

All models include a provision for adding an alarm
or automatic water feeder.

Control Voltage:

120 VAC

HZ:

50/60

Probe Sensitivity:

For models with red (low water) and amber (test) 
lights: 3,000 ohm

For models with red (low water) and green (power) 
lights: 7,000 ohm

Control Power Consumption:

For models with red (low water) and amber (test) 
lights: 3 VA

For models with red (low water) and green (power) 
lights: 3.6 VA

Motor Switch Rating (Amperes)

Model

Voltage

Full Load

Locked Rotor

Pilot Duty

120 VAC

120 VAC

7.5

43.2 

125 VA at

240 VAC

3.75 

21.6 

120 or 240 VAC

50 or 60 Hz

The Series 800 controls provide con-
tinuous protection against low water
conditions for residential, commercial
and industrial applications. Newer
models feature increased probe 
sensitivity to prevent nuisance shut-
downs, and a new test feature that
diagnoses shorted probe problems at
installation. The user-friendly diag-
nostic LEDs simplify installation and
troubleshooting, ensuring proper
operation and saving time.

Green

(Power On)

Red

(Low Water)

Amber

(Test)

Red

(Low Water)

Older Models

New Models

Temperature:

Storage: -40˚F to 120˚F (-40˚C to 49˚C)
Ambient: 32˚F to 120˚F (0˚C to 49˚C)

Humidity:

85% (non-condensing)

Electrical Enclosure Rating:

NEMA 1 General Purpose

Содержание McDonnell & Miller GuardDog PS-801 Series

Страница 1: ...for proper operation of all of the limit and operating controls before leaving the site We recommend that secondary redundant Low Water Cut Off controls be installed on all steam boilers with heat in...

Страница 2: ...st lights 3 000 ohm For models with red low water and green power lights 7 000 ohm Control Power Consumption For models with red low water and amber test lights 3 VA For models with red low water and...

Страница 3: ...ine suitable tapping for the probe 2 Locate probe in supply piping using a tee fitting STEP 1 Locating and Installing the Probe 3 1 4 6mm 1 4 6mm A E A F c Using a wrench tighten the probe A into the...

Страница 4: ...clockwise so that the slots in the control base are firmly under the screw heads Tighten the mounting screws F to approximately 2 ft lb 2 6 N m d Identify a desirable location to mount the control as...

Страница 5: ...l shock turn off the electrical power before making electrical connections This low water cut off must be installed in series with all other limit and operating controls installed on the boiler After...

Страница 6: ...ing of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C Failure to follow this warning could cause property damage personal injury or death WARNING Models with Red low water and Amber test Li...

Страница 7: ...CUIT C B D A N 120 VOLT CIRCUIT Connect Hot wire A of 120 volt circuit to terminal H Connect Neutral wire B of 120 volt circuit to terminal N Connect wire C from beginning of Burner circuit thermostat...

Страница 8: ...r LED BB on top of the control housing G 1 If the amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pu...

Страница 9: ...ntinue to flash for 15 seconds DOM and then turn OFF 4 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low water...

Страница 10: ...light will flash for 15 seconds DOB and then turn OFF 7 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low wate...

Страница 11: ...turn ON as long as there is water on the probe Testing Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button to activate test...

Страница 12: ...e adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAUTION C...

Отзывы: