7
B
H
1
2
3
4
5
BURNER
CIRCUIT
C
D
B
A
N
120 VOLT
CIRCUIT
L
1
L
2
T
1
T
2
24 VOLT
TRANSFORMER
(BY OTHERS)
E
• Connect wire (A) of 120 volt circuit to terminal (1) and
terminal (L1) of transformer.
• Connect wire (B) of 120 volt circuit to terminal (2) and
terminal (L2) of transformer.
• Connect wire (C) to terminal (3) and terminal (T1) of transformer.
• Connect wire (D) from beginning of Burner circuit (thermostat,
gas valve, limits, etc.) to terminal (5).
• Connect wire (E) from end of Burner circuit to terminal (T2) of
transformer.
PS-801/851 with 24 Volt Burner Circuit with Red (Low Water) and
Amber (Test) Lights
G
e.
Place the cover on the control housing, and,
using a flathead screwdriver, tighten the two
(2) screws into the control housing and
cover (G) to approximately 2 ft•lb (2.6 N•m).
INSTALLATION COMPLETE
E
H
N
H
C
W
B
BURNER
CIRCUIT
C
B
D
A
N
120 VOLT
CIRCUIT
• Connect Hot wire (A) of 120 volt circuit to terminal (H).
• Connect Neutral wire (B) of 120 volt circuit to terminal (N).
• Connect wire (C) from beginning of Burner circuit (thermostat,
gas valve, limits, etc.) to terminal (B).
• Connect wire (D) from end of Burner circuit to terminal (N).
• Connect jumper wire (E) to terminals (H) and (C).
PS-801/851 with 120 Volt Burner Circuit with Red (Low Water) and
Green (Power) Lights
E
H
N
H
C
W
B
BURNER
CIRCUIT
E
C
B
A
N
120 VOLT
CIRCUIT
L
1
L
2
T
1
T
2
24 VOLT
TRANSFORMER
(BY OTHERS)
D
• Connect hot wire (A) of 120 volt circuit to terminal (H) and
transformer terminal (L1).
• Connect neutral wire ‘B’ of 120 volt circuit to terminal (N) and
transformer terminal (L2).
• Connect wire (C) from beginning of Burner circuit
(thermostat, gas valve, limits, etc.) to terminal (B).
• Connect wire (D) from end of Burner circuit to transformer
terminal (T2).
• Connect wire (E) from transformer terminal (T1) to
terminal (C).
PS-801/851 with 24 Volt Burner Circuit with Red (Low Water) and
Green (Power) Lights