background image

If control fails to operate as required, perform the following diagnostic checks:

1.

Check to be sure that the water level in the boiler is at or above the level of the probe.

2.

Re-check all wiring to ensure proper connections as specified in boiler manufacturer’s wiring diagrams 
or these instructions.

3.

Check to ensure that Teflon

®

tape has not been used on the threaded connection of the electrode 

to the boiler.

4.

Re-check the electrical ground connection for the remote sensor and control unit.

5.

Check the quality of the boiler water to ensure adequate conductance.

Troubleshooting

Replace Probe if:
• Teflon® insulator is cracked or worn.
• Probe is loose.
Failure to follow this caution could cause property damage, personal injury or death.

CAUTION

!

Clean probe by wiping with non-abrasive cloth and rinsing with clean water. DO NOT
use sharp instruments to remove any accumulations of rust or scale.

NOTE

MAINTENANCE

SCHEDULE:

Test the low water cut-off annually or more frequently.

Remove and inspect the self-cleaning probe every 5 years.

Replace probe every 10 years.

Replace the lo water cut-off control box every 15 years.

ITT

8200 N. Austin Ave.
Morton Grove, IL 60053
tel:  847-966-3700
fax: 847-966-9052
www.mcdonnellmiller.com

McDonnell & Miller

©2007 ITT Corporation 

Printed in U.S.A.  11-07   246780

Содержание McDonnell & Miller GuardDog PS-801 Series

Страница 1: ...for proper operation of all of the limit and operating controls before leaving the site We recommend that secondary redundant Low Water Cut Off controls be installed on all steam boilers with heat in...

Страница 2: ...st lights 3 000 ohm For models with red low water and green power lights 7 000 ohm Control Power Consumption For models with red low water and amber test lights 3 VA For models with red low water and...

Страница 3: ...ine suitable tapping for the probe 2 Locate probe in supply piping using a tee fitting STEP 1 Locating and Installing the Probe 3 1 4 6mm 1 4 6mm A E A F c Using a wrench tighten the probe A into the...

Страница 4: ...clockwise so that the slots in the control base are firmly under the screw heads Tighten the mounting screws F to approximately 2 ft lb 2 6 N m d Identify a desirable location to mount the control as...

Страница 5: ...l shock turn off the electrical power before making electrical connections This low water cut off must be installed in series with all other limit and operating controls installed on the boiler After...

Страница 6: ...ing of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C Failure to follow this warning could cause property damage personal injury or death WARNING Models with Red low water and Amber test Li...

Страница 7: ...CUIT C B D A N 120 VOLT CIRCUIT Connect Hot wire A of 120 volt circuit to terminal H Connect Neutral wire B of 120 volt circuit to terminal N Connect wire C from beginning of Burner circuit thermostat...

Страница 8: ...r LED BB on top of the control housing G 1 If the amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pu...

Страница 9: ...ntinue to flash for 15 seconds DOM and then turn OFF 4 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low water...

Страница 10: ...light will flash for 15 seconds DOB and then turn OFF 7 The burner will turn ON as long as there is water on the probe Warning To prevent flooding never use a water feeder with a manual reset low wate...

Страница 11: ...turn ON as long as there is water on the probe Testing Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button to activate test...

Страница 12: ...e adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAUTION C...

Отзывы: