Dimensioning the inlet and outlet ducts
In the list that follows, you will the characteristic losses of load of the original fume venting accessories,
expressed as equivalence in meters (m).
Se fossero previsti accessori di fumisteria originali aggiuntivi rispetto a quelli raffigurati, nel cal-
colo della lunghezza totale devono essere considerate le relative perdite di carico equivalenti,
espresse come equivalenza in metri (m) nell’elenco seguente.
In the case where pipes are installed with non-original accessories (this is allowed by the boiler’s C6
type-approval),
but, in any case, absolutely certified for condensation,
the installer must consider the
losses of load specified by the manufacturer of these accessories, dimensioning the suction and dis-
charge system so that the total loss of load (expressed in Pa) is between the head loss values of the
boiler fan specified in the paragraph "Technical data" on page 45.
Original accessories for separated systems (advises even for type C6):
Connector between boiler and Ø80mm inlet pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.3 m - 2 Pa
Connector between boiler and Ø80mm outlet pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.7 m - 5 Pa
Separate system Ø 60 mm (original accessories):
Reduction from Ø80mm to Ø60mm on inlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.4 m
Reduction from Ø80mm to Ø60mm on outlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.7 m
Linear section or extension Ø60mm length 0.5m on inlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5 m
Linear section or extension Ø60mm length 0.5m on outlet
. . . . . . . . . . . . . . . . . . . . . . . . . . .0.5 m
Linear section or extension Ø60mm length 1m on inlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.9 m
Linear section or extension Ø60mm length 1m on outlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 m
Linear section or extension Ø60mm length 2m on inlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8 m
Linear section or extension Ø60mm length 2m on outlet
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 m
90° bend Ø60mm on inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 m
90° bend Ø60mm on outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.6 m
45° bend Ø60mm on inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5 m
45° bend Ø60mm on outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.8 m
T-shaped condense collector Ø60mm on discharge
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 m
Inlet terminal Ø60mm (length 1 m)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4 m
Horizontal outlet terminal Ø60mm (length 1 m)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4 m
Vertical outlet terminal Ø60mm (length 1 m)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 m
Coaxial system Ø100/60mm (original accessories):
Flanged coaxial connector Ø100/60mm (starting vertically)
. . . . . . . . . . . . . . . . . . . . . . . . . . . 0 m
Flanged coaxial 90° bend Ø100/60mm (starting horizontally)
. . . . . . . . . . . . . . . . . . . . . . . . . . 2 m
Coaxial linear section or extension Ø100/60mm (length 1 m)
. . . . . . . . . . . . . . . . . . . . . . . . . . 1 m
90° coaxial bend Ø100/60mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 m
45° coaxial bend Ø100/60mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5 m
Horizontal condense collector Ø100/60mm
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 m
Horizontal inlet + outlet coaxial terminal Ø100/60mm (length 1 m)
. . . . . . . . . . . . . . . . . . . .1.5 m
Vertical inlet + outlet coaxial terminal Ø125/80mm (length 1 m, connector Ø100/60mm)
. . 1 m