Green Heating Technology
34
• wait (approximately five seconds) that the display shows
“PO”
(POwer) flashing (moreover, both
the
GREEN
and
RED
indicators flash to short “pulses”).
•
when the display shows
“PO”
flashing, within 15 seconds turn the Summer/Winter
knob on
the MAXIMUM value of the scale of the heating
(fully clockwise). The
service
indication ap-
pears on the display and the burner ignites to the maximum output not modulated (the
YELLOW
indicator turns on);
• on the display, the number 99 flashes, indicating the current maximum heating output setting; it’s
possible to change the maximum power output by acting directly on the Summer/Winter
knob
within the scale of the heating
;
REMARK: the value from 00 to 99 that appears on the display during the setting, is foreseen to be
read at the end of the adjustment and to be eventually re-used as a quick reference to set the
boiler again to the same heating power.
•
do NOT move the Summer/Winter
knob for about
30 seconds
, until the number on the dis-
play stops flashing (also the
GREEN
indicator stops flashing and stays on). During this time,
check
that the pressure displayed on the manometer remains stabilized on the correct value. If further
pressure adjustment should be needed, turn the knob and wait again 30 seconds and the end of
flashing;
• to confirm and save the setting, turn the Hot Water knob
on the scale
; the burner will
turn off for a moment. Wait (about 5 seconds) that both the
GREEN
and
RED
indicators stay on
for about 5 seconds (this is the confirmation that the burner pressure for heating is stored), then
the
RED
indicator
turns off;
4.
to switch off the burner, turn the Summer/Winter knob
to the
position.
The MAX power for the heating system is now adjusted.
The whole procedure should be completed within 15 minutes from the start. If you exceed this time, or
in case of mistakes, the new pressure will not be stored and it will be necessary to repeat the procedure
from the beginning, by turning the Summer/Winter knob
on
and the Hot Water knob
on
the scale
.
Power input / display / fan rpm table
HEAT INPUT
FAN RPM
INDICATIVE
DISPLAY
VALUE
kW
kcal/h
Natural gas
G20
Commercial
Propane G31
City Ma
x 26 K
MIN. 5.3
4558
1500
1600
0
7.45
6416
1930
2030
10
9.5
8187
2360
2460
20
11.6
9959
2790
2890
30
13.6
11730
3220
3320
40
15.7
13502
3650
3750
50
17.8
15274
4080
4180
60
19.8
17045
4510
4610
70
21.9
18817
4940
5040
80
23.9
20588
5370
5470
90
MAX. 26.2
22532
5800
5900
99