Guideline for Connection and Use of Photometer 

 

2. 1.  Field of Use 

 
Photometer  is  designed for measuring  and  regulation  of  traffic  area  illumination. Based 
on  L

20

  measurement  according  to  CIE  standard  it  establishes  adequate  illumination  at 

any time of day and any light conditions. Integrated logic controller and software provide 
complete solution for tunnel lighting regulation with no external controller necessary.  
Photometer FM-4 is provided with 4-channel 230 V AC contactor-driving outputs for local 
lighting  control,  programmable.  Full  function  control,  measuring  range,  output  channel 
switching and time averaging interval are PC programmable using software provided. 

2. 2.  Mounting and Placement 

 
Photometer comes with wall/pole fixture; special pole fixture is also available (optional).  
When used for tunnel entrance portal-lighting measurement, the photometer is installed 
at  the stopping  distance  before  the  tunnel  entrance. It should  be  pointed  directly  to the 
entrance.  Mounting  on  pole,  take  special  care  for  proper  pole  grounding,  including  any 
foldings or joints! 
When it is used to measure in-tunnel light conditions, it should be mounted at the height 
of app. 4.5 metres and pointed to the spot one reach in 3 seconds at maximum allowed 
speed.  In  this  case  the  driver’s  view  cannot  be  simulated  accuratley  due  to  mounting 
height and measuring result shlold be adopted by correction factor (usually between 1.05 
and  1.20).  For  in-tunnel  use,  especially  in  long  tunnels  choose  full-stainless  steel 
hausing option. 
Once mounted, undisturbed view-field of the photometer must be provided. There should 
be no light sources, either any light reflecting objects in the view-field of the photometer. 
Any of those can considerably affect light measuring accuracy. 

2. 3.  Connections 

 
Photometer  is  connected  to  the  mains  power  supply  230  V  AC  and  to  the  tunnel  light 
controlling system. All connections are done from the back side with cover removed. Cables 
of 3-9 leads and minimum 0.75 mm

2

 must be used for 230 V AC power outputs. Maximum 

connection distance is up to 400 metres.  
 
After  final  connection  and  successful  commition  place  desiccant  bag  provided  in  the 
photometer’s  housing  and  push  it  towards  front  window.  Take  care  it  is  not  touching  any 
electrical  part!  Cable  inlet-glands  and  back  cover  must  be  well  tightened  after  final 
connection! 
 
 
 
         
 

 

Содержание Photometer FM-4

Страница 1: ...Operating manual Photometer FM 4 Litostrojska cesta 44 d SI 1000 Ljubljana T 386 1 514 18 00 F 386 1 514 18 04 info itaia si www itaia si ELECTRONICS RESEARCH DEVELOPMENT...

Страница 2: ......

Страница 3: ...ation Port 6 2 4 2 Use of 230 V AC Contactor Outputs 7 2 5 CALIBRATION 7 3 PC SOFTWARE STREET LIGHT VISION 8 3 1 WRITING DATA TO THE PHOTOMETER 9 3 2 READING DATA FROM THE PHOTOMETER 10 3 3 SETTING UP...

Страница 4: ...F DEVICE MUST BE CARIED OUT BY QUALIFIED PERSONNEL WHEN CONNECTING DISCONNECT ELECTRICAL POWER FIRST DO NOT BLOCK ACCESS TO ELECTRICAL PARTS USED FOR EMERGENCY STOP CLEANING AND MAINTENANCE ALL METAL...

Страница 5: ...s disconnected during the time of mounting and connecting Check the voltage presence with an instrument Check grounding connection Provide protection against touching the parts under voltage Qualified...

Страница 6: ...F 386 1 514 18 04 info itaia si www itaia si Declaration of Conformity The device complies with relevant European directives CE declaration of conformity Electromagnetic compatibility ULRS no 132 2006...

Страница 7: ...foldings or joints When it is used to measure in tunnel light conditions it should be mounted at the height of app 4 5 metres and pointed to the spot one reach in 3 seconds at maximum allowed speed I...

Страница 8: ...6 contactor out D 230 V AC contactor out D 7 out out C 230 V AC contactor out C 8 out B 230 V AC contactor out B 9 out A 230 V AC contactor out A 10 PC GND 0 V DC programming control 11 RS 232 RX 12...

Страница 9: ...r the user 2 4 1 Serial Communication Port The photometer s selectable communication port can be configured for RS 232 or RS 485 Set jumpers J1 J3 to select the protocol Connection distance can be up...

Страница 10: ...LEDs and contactor outputs Green LEDs indicate estimated switch level combination no averaging delay due to current light condition Red LEDs indicate current status of 230 V AC outputs averaging affec...

Страница 11: ...tor photometer s working parameters Install the software to any folder on the computer running MS Windows 2000 or higher The program is executed by clicking SLV icon Graphical user interface of the pr...

Страница 12: ...th the combination used when the highest level specified is exceeded see Picture 3 Table 2 Averaging interval is the moving average of light level calculating time in minutes before contactor outputs...

Страница 13: ...ice matching ID After reading data is refreshed in all fields Light Level Read Manual setting reads light level and any other device s parameter by clicking Read button Use Auto setting to read light...

Страница 14: ...For RS 232 485 settings on the photometer see 2 4 1 Serial communication Port in this manual Picture 4 Photometer System Settings StreetLightVision software selects COM1 as the default If port is occu...

Страница 15: ...edure when there is another device with the same ID on the bus only Write new ID into the field and click New ID button The numerical data within 0 255 can be selected Make sure to write down new ID I...

Страница 16: ...uto to activate the data logging Table graph and data file are updated every time when Light Level data is read from photometer Logging interval is time in minutes between two readings The numerical d...

Страница 17: ...nths interval clean the housing 1 year interval and recalibrate 3 year interval Note The device requires regular checking and maintenance Keep your maintenance and service log up to date Shorten check...

Страница 18: ...rial port Note No communication note appears by unsuccessful communication with photometer check ID number of the device check power supply and data connection to the photometer Note Communication err...

Страница 19: ...A 5x20 mm Casing IP67 Aluminium Stainless steel ABS Size W x H x D 395 x 135 230 x 145 mm Weight 2 8 kg Fixture wall X Y adjustable fixture pole optional Communication port RS 232 485 9600 bps Contact...

Страница 20: ...conditions Production year is visible on the back side sticker Deteriorated or ruined device dispose to the place for industry electronic components disposal according to local regulation Components p...

Страница 21: ...Safety requirements for electrical equipment for measurement control and laboratory use Part1 General requirements SIST EN 61000 3 2 2006 EMC Part 3 2 Limits for harmonic current emissions equipment...

Страница 22: ...ist in case of improper use or use in discordance to this manual in case of mechanical damage in case of consequential damage due to failure or damage of other devices in case of natural or environmen...

Страница 23: ...V 1 2 rev 12 2012...

Страница 24: ...Litostrojska cesta 44 d SI 1000 Ljubljana T 386 1 514 18 00 F 386 1 514 18 04 info itaia si www itaia si...

Отзывы: