34
Clearance to Insulation & Vapor Barriers
FIGURE 75
The Magnum Series firebox backwall, side walls and the smoke dome back require 1 1/2” clearance. (Figure 74)
Keep all insulaion and vapor barriers a minimum 3” away from all Iskern surfaces. (Figure 75)
Keep all insulation, vapor barriers, “house wrap” paper and other insulating type membranes and products, including
fiberglass, cellulose and other insulation, a minimum of three inches (3”) away from all MAGNUM surfaces. (Figure 75)
When MAGNUM fireplace installations are surrounded by walls that are to be insulated, the walls must have enough clearance to
the Isokern unit in order to maintain the three inch (3”) minimum clearance to insulation. (Figure 75) Never spray the MAGNUM
fireplace with any type of sealer, insulation or other material.
If insulation or vapor barriers are used in walls surrounding the MAGNUM fireplace, it is strongly recommended that the walls be
sheathed with gypsum board, plywood, particle board or other material on the side facing the Isokern to assure the insulation and
vapor barriers remain in place and a minimum of 3” away from the unit.