ise smart connect Modbus Vaillant
Modbus TCP/IP
Order No.
S-0002-007
Product Manual Page 21 (45)
4.5.4.2
Holding Registers (R/W)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
7
Heating circuit operating
mode
2
8
Day target room
temperature
uint16_t
2
5
– 50
°C
9
Set-back temperature
uint16_t
2
5
– 50
°C
10-11
Heating curve
IEEE 754 single float 2
0.1
– 4.0
0.05
12
Maximum target flow
temperature
uint16_t
2
15
– 80
°C
13
Minimum target flow
temperature
uint16_t
2
15
– 80
°C
14
Outside temperature
switch-off threshold
uint16_t
2
5
– 50
°C
4.5.5
Unit ID 12, 14
– 18: Vaillant VR90 heating circuit 2, 4 – 8
4.5.5.1
Input Registers (R)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
1
eBUS error
2
eBUS last error
3
Room temperature sensor
state
2
4
Room temperature sensor
value
int16_t
2
-2048
–
2048
°C
4.6
Datatypes
4.6.1
eBusErrorState
Value Description
0
No error / device found
1
Error during eBUS communication / device not found
4.6.2
eBusError
Value Description
0
No Error
1
geoTHERM/3, VR60 or VR90 not found
2
No compatible geoTHERM/3, VR60 or VR90 found
3
Error in communication with the ise eBUS Adapter
4
eBUS cable not connected
5
No answer from eBUS
7
Value not permitted