ise smart connect Modbus Vaillant
Modbus TCP/IP
Order No.
S-0002-007
Product Manual Page 19 (45)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
55
Mixer activation
2
56
Heating circuit
pump status
2
4.5.1.2
Holding Registers (R/W)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
57
Brine pump speed control
uint16_t
2
7
– 100
%
58
Compressor hysteresis
uint16_t
2
3
– 15
K
59
Energy integral since
compressor started
int16_t
2
-250
– -5
°min
60
CH pump speed control
uint16_t
2
30
– 100
%
61
Heating circuit operating
mode
2
62
Day target room
temperature
uint16_t
2
5
– 50
°C
63
Set-back temperature
uint16_t
2
5
– 50
°C
64-65
Heating curve
IEEE 754 single float 2
0.1
– 4.0
0.05
66
Maximum target flow
temperature
uint16_t
2
15
– 80
°C
67
Minimum target flow
temperature
uint16_t
2
15
– 80
°C
68
Outside temperature
switch-off threshold
uint16_t
2
5
– 50
°C
4.5.2
Unit ID 2: Vaillant geoTHERM/3 domestic hot water
4.5.2.1
Input Registers (R)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
1
Cylinder hot water
temperature sensor state
2
2
Cylinder hot water
temperature sensor value
int16_t
2
-2048
–
2048
°C
3
3-way valve setting
2
4.5.2.2
Holding Registers (R/W)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
4
Hot water circuit
operating mode
2
5
Target hot water
temperature
uint16_t
2
30
– 65
°C
6
Maximum hot water
target value
uint16_t
2
40
– 75
°C