ise smart connect Modbus Vaillant
Modbus TCP/IP
Order No.
S-0002-007
Product Manual Page 18 (45)
Addr.
Name
Datatype
Polling
interval
[min]
Range
Reso-
lution
Unit
21
Pressure compressor low
sensor state
2
22-23
Pressure compressor low
sensor value
IEEE 754 single float 2
0
– 65.5
0.1
bar
24
Compressor outlet
temperature sensor state
2
25
Compressor outlet
temperature sensor value
int16_t
2
-2048
–
2048
°C
26
External top cylinder
temperature sensor state
2
27
External top cylinder
temperature sensor value
int16_t
2
-2048
–
2048
°C
28
External bottom cylinder
temperature sensor state
2
29
External bottom cylinder
temperature sensor value
int16_t
2
-2048
–
2048
°C
30
Error history 1
15
31
Error history 2
15
32
Error history 3
15
33
Error history 4
15
34
Error history 5
15
35
Error history 6
15
36
Error history 7
15
37
Error history 8
15
38
Error history 9
15
39
Error history 10
15
40
Status heat pump
2
41-42
Earned environment
energy
uint32_t
60
kWh
43
Outside temperature
sensor state
15
44
Outside temperature
sensor value
int16_t
15
-2048
–
2048
°C
45
Flow temperature
sensor state
2
46
Flow temperature
sensor value
int16_t
2
-2048
–
2048
°C
47
Return temperature
sensor state
2
48
Return temperature
sensor value
int16_t
2
-2048
–
2048
°C
49
Heating circuit pressure
sensor state
2
50-51
Heating circuit pressure
sensor value
IEEE 754 single float 2
0
– 65.5
0.1
bar
52
Energy integral value
int16_t
2
°min
53
VF2 flow temperature
sensor state
2
54
VF2 flow temperature
sensor value
int16_t
2
-2048
–
2048
°C