ise smart connect Modbus Vaillant
Configuration
Order No.
S-0002-007
Product Manual Page 12 (45)
3
Configuration
Configuration of the ise smart connect Modbus Vaillant system components is divided into the following
steps:
Preparations:
For explana-
tions, see
1
Installing ise eBUS Adapter. Connect the ise smart connect Modbus Vaillant
with the ise eBUS Adapter via the USB interface.
Use the supplied USB cable as standard.
Please note that the use of USB
cables with a length of more than 3 m is generally not permitted.
Chapter 2
2
Mount ise smart connect Modbus Vaillant; connect it to auxiliary voltage.
Important note: Please ensure that the device is only supplied with voltage by
a dedicated power supply unit. Do not use the auxiliary voltage output of a
KNX power supply unit which is also supplying a KNX line.
Chapter 2.3
3
Connect the ise eBUS Adapter with the eBUS in the intended junction box.
Important note: The maximum length of the eBUS connection cable is 125 m.
Chapter 2.5
4
Install the ise smart connect Modbus Vaillant on the IP network and make
settings in the router of the IP network if necessary.
Configuration via website:
After installing the device and connecting the power supply and Ethernet, the device can be config-
ured via the website:
1
Set the IP address, the IP subnet mask and the default gateway address of
the ise smart connect Modbus Vaillant or select "DHCP active" to obtain
automatically an IP address from the router.
Chapter 3.1
2
Configuration of system dimensioning (additional data points and modules)
Chapter 3.2
3
Configuration of the Modbus TCP/IP port if necessary (default port is 502).
Chapter 3.3
4
Configuration of your building management system (BMS) to access the ise
smart connect Modbus Vaillant with a Modbus TCP/IP client.
Chapter 4