ise smart connect Modbus Vaillant
Modbus TCP/IP
Order No.
S-0002-007
Product Manual Page 22 (45)
4.6.3
sensorState
Value Description
0
No fault
85
Short-circuit
170
Interrupt
4.6.4
status
Value Description
0
Off
1
On
4.6.5
DTC_EHP
The “error number geoTHERM/3” is the error number displayed on the geoTHERM/3 controller.
Value Error number
geoTHERM/3
Description
514
30
Error comp inlet sensor
515
31
Error evaporator sensor
516
32
Error heat source outlet sensor
517
40
Error comp outlet sensor
518
41
Error heat source inlet sensor
519
42
Error HP return sensor
520
43
Error HP flow sensor
521
44
Error AF sensor
522
45
Error SP sensor
523
46
Error VF1 sensor
524
47
Error RF1 sensor
525
48
Error VF2 sensor
526
49
Sensor fault: TCoilLiquidOpen
527
50
Error heat source outlet sensor
528
51
Error condenser sensor
529
60
Error Heat source anti freezing protection : Delta T6-T7
530
61
Error Heat source anti freezing protection : T5<4°C
531
62
Error Heat source anti freezing protection : T6<-10°C
532
63
Error No water flow
533
70
Error Abnormal cooling of the C-H circuit
534
71
Building circuit: Floor protect. active
535
72
Error C-H flow temperature too high for floor heating
536
80
Error Compressor outlet overheat
537
81
Error Refrigerant pressure too high.
538
82
Error Refrigerant pressure too high. Check C-H pump
539
83
Error Refrigerant pressure too low
540
90
Error C-H pressure too low P14bar
541
91
Error Pressure brine too low
542
92
Error C-H return temperature too high
543
93
Error Fan overheat thermostat open
544
94
Error or two phase are missing
545
95
Error Wrong phase order
546
96
Error Refrigerant pressure sensors fault
547
20
Op Interlock: Heat source anti freezing protection : Delta T6-T7