Optidrive VTC – User Guide 

26 

                                          

www.invertek.co.uk 

 

9.

 

Technical data 

9.1.

 

Environmental 

 
Operational ambient temperature range: -10 … 50°C, Frost and condensation free 
Storage ambient temperature range: -40 … 60°C 
Maximum altitude: 2000m.  Derate above 1000m : 1% / 100m 
Maximum humidity: 95%, non-condensing 

9.2.

 

Rating tables 

200-240V ±10% - 1 Phase Input 
3 Phase Output 

Model 

(kW) 

kW 

Model 

(HP) 

HP 

Frame 

Size 

Nominal 

Input 

Current 

Fuse or 

MCB 

(type B) 

Supply 

Cable 

Size 

Nominal 

Output 

Current 

110% 

Output 

Current 

60 secs 

Motor 

Cable 

Size 

Max 

Motor 

Cable 

Length 

Min 

Brake 

Res 

Value 

 

 

 

 

 

Amps 

Amps 

mm

2

 

Amps 

Amps 

mm

2

 

Ω 

ODV-22150 

1.5 

ODV-22020-USA 

19.3 

20 

7.7 

1.5 

100 

33 

ODV-22220 

2.2 

ODV-22030-USA 

28.8 

32 

10.5 (9) 

11.6 (9.9) 

1.5 

100 

22 

NOTE 

For cUL compliance, fuse type Bussmann KTN-R / KTS-R or equivalent must be used 

 

200-240V ±10% - 3 Phase Input drive model set for 1 Phase Operation (See section 5.8) 
3 Phase Output 

Model 

kW 

Model 

HP 

Frame 

Size 

Nominal 

Input 

Current 

Fuse or 

MCB 

(type B) 

Supply 

Cable Size 

Nominal 

Output 

Current 

110% Output 

Current 60 

secs 

Motor 

Cable Size 

Max Motor 

Cable 

Length 

Min 

Brake 

Res 

Value 

 

 

 

 

 

Amps 

Amps 

mm

2

 

Amps 

Amps 

mm

2

 

Ω 

ODV-32030 

1.5 

ODV-32040-USA 

19.3 

20 

7.7 

1.5 

100 

15 

ODV-32040 

2.2 

ODV-32050-USA 

28.8 

35 

9.9 

1.5 

100 

15 

ODV-32055 

ODV-32075-USA 

31.3 

35 

12.5 (12) 

13.8 (13.2) 

2.5 

100 

15 

ODV-42075 

ODV-42100-USA 

58.3 

50 

10 

19.5 

21.5 

2.5 

100 

ODV-42110 

5.5 

ODV-42150-USA 

7.5 

67.6 

80 

16 

23 

25.3 

100 

ODV-42150 

7.5 

ODV-42200-USA 

10 

87.0 

100 

25 

30.5 

33.6 

10 

100 

ODV-42185 

ODV-42250-USA 

12 

96.1 

100 

25 

36 

39.6 

10 

100 

ODV-42220 

11 

ODV-42300-USA 

15 

115.4 

125 

35 

45 

49.5 

16 

100 

ODV-52300 

15 

ODV-52400-USA 

20 

146.1 

160 

50 

55 

60.5 

16 

100 

ODV-52370 

18.5 

ODV-52500-USA 

25 

187.8 

200 

70 

75 

82.5 

25 

100 

ODV-52450 

22 

ODV-52600-USA 

30 

220.6 

250 

90 

90 

99 

25 

100 

NOTE 

Values shown in brackets are the maximum for UL applications 
For cUL compliance, fuse type Bussmann KTN-R / KTS-R or equivalent must be used 

 

200-240V ±10% - 3 Phase Input 
3 Phase Output 

Model 

kW 

Model 

HP 

Frame 

Size 

Nominal 

Input 

Current 

Fuse or 

MCB 

(type B) 

Supply 

Cable Size 

Nominal 

Output 

Current 

110% Output 

Current 60 

secs 

Motor 

Cable Size 

Max Motor 

Cable 

Length 

Min 

Brake 

Res 

Value 

 

 

 

 

 

Amps 

Amps 

mm

2

 

Amps 

Amps 

mm

2

 

Ω 

ODV3-22150 

1.5 

ODV3-22020-USA 

9.2 

10 

2.5 

7.7 

1.5 

100 

33 

ODV3-22220 

2.2 

ODV-22030-USA 

13.7 

16 

10.5 (9) 

11.6 (9.9) 

1.5 

100 

22 

ODV-32030 

ODV-32040-USA 

16.1 

20 

14 

15.4 

1.5 

100 

15 

ODV-32040 

ODV-32050-USA 

17.3 

20 

18 

19.8 

1.5 

100 

15 

ODV-32055 

5.5 

ODV-32075-USA 

7.5 

25 

25 

25 (24) 

27.5 (26.4) 

2.5 

100 

15 

ODV-42075 

7.5 

ODV-42100-USA 

10 

46.6 

50 

10 

39 

42.9 

2.5 

100 

ODV-42110 

11 

ODV-42150-USA 

15 

54.1 

63 

16 

46 

50.6 

100 

ODV-42150 

15 

ODV-42200-USA 

20 

69.6 

80 

25 

61 

67.1 

10 

100 

ODV-42185 

18.5 

ODV-42250-USA 

25 

76.9 

80 

25 

72 

79.2 

10 

100 

ODV-42220 

22 

ODV-42300-USA 

30 

92.3 

100 

35 

90 

99 

16 

100 

ODV-52300 

30 

ODV-52400-USA 

40 

116.9 

125 

50 

110 

121 

16 

100 

ODV-52370 

37 

ODV-52500-USA 

50 

150.2 

160 

70 

150 

165 

25 

100 

ODV-52450 

45 

ODV-52600-USA 

60 

176.5 

200 

90 

180 

198 

25 

100 

NOTE 

Values shown in brackets are the maximum for UL applications 
For cUL compliance, fuse type Bussmann KTN-R / KTS-R or equivalent must be used 

 

 

Содержание Optidrive VTC

Страница 1: ...User Guide Optidrive VTC Variable Torque Control AC Variable Speed Drive 1 5 160kW 2 250HP Installation and operating instructions...

Страница 2: ...ired Use screened motor cable Note For motor cable lengths greater than 100m an output dv dt filter must be used part number OD OUTFx please refer to the Invertek Stock Drives Catalogue for further de...

Страница 3: ...tings 13 5 5 Terminal Control 14 5 6 Keypad Control 14 5 7 Motor Autotuning 15 5 8 Operation of Three Phase drives on Single Phase Supplies 15 6 PARAMETERS 16 6 1 Parameter Group 1 Basic Parameters 16...

Страница 4: ...he enable input signal is present The STOP function does not remove potentially lethal high voltages ISOLATE the drive and wait 10 minutes before starting any work on it Electric shock hazard Disconne...

Страница 5: ...V 10 3 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size ODV3 22150 xx 1 5 ODV3 22020 USA 2 7 2 ODV3 22220 xx 2 2 ODV3 22030 USA 3 10 5 9 2 ODV 32030 xx 3 0 ODV 32040 USA 4...

Страница 6: ...ht 260mm Width 171mm Depth 175mm A 210mm B 163mm Incoming Power Terminals C 25mm Help Card Keypad Display See Section 0 on page 12 Footprint View RJ11 Connector See Section Infra Red Interface Weight...

Страница 7: ...s N1 160mm Centres N2 105mm Slots D1 8 5 x 22mm Busbar Connections Length A1 40mm Connection Diameter D2 9mm Note The choke is always supplied with the drive and MUST be used 3 2 Before Installation C...

Страница 8: ...water from all directions High moisture salt or chemical content environments should use a suitably sealed non vented enclosure Enclosure Front View Enclosure Side View The enclosure design and layou...

Страница 9: ...unding point for the motor cable shield The motor cable shield connected to this terminal drive end should also be connected to the motor frame motor end Use a shield terminating or EMI clamp to conne...

Страница 10: ...r Terminal Box Connections Most general purpose motors are wound for operation on dual voltage supplies this is indicated on the nameplate of the motor This operational voltage is normally selected wh...

Страница 11: ...tput 4 Digital Input 3 Analog Input 2 Digital Logic 1 input voltage range 8 to 30V DC Logic 0 input voltage range 0 to 8 V DC Analog 0 to 10V 0 to 20mA or 4 to 20mA 5 24V User Output 24V 100mA 1k mini...

Страница 12: ...n parameter edit mode RESET STOP Used to reset a tripped drive When in Keypad mode is used to Stop a running drive START When in keypad mode used to Start a stopped drive or to reverse the direction o...

Страница 13: ...isplay shows Press Display shows Set Parameter to minimum value Any numerical value Whilst editing a parameter value The parameter is set to the minimum value When editing P1 01 Display shows Press Di...

Страница 14: ...be adjusted anywhere between minimum and maximum speed using the potentiometer To display motor current Amps briefly press the Navigate key Press again to display the motor power Press again to retur...

Страница 15: ...trol mode is changed P4 01 User Selected Autotune The user can program the drive to carry an autotune if required as follows Ensure the motor nameplate values are correctly entered in P1 07 Motor Rate...

Страница 16: ...el ramp time P1 06 Energy Optimiser 0 Disabled 1 Enabled 0 Disabled When enabled automatically reduces applied motor voltage on light load Minimum value is 50 of nominal P1 07 Motor rated voltage 0 20...

Страница 17: ...above zero speed Options 4 to 6 the Digital output is enabled using the level set in P2 12h and P2 12L Analog Output Mode 7 Motor Speed 0 to 10V 0 to P 01 8 Motor Current 0 to 10V 0 to 200 of P1 08 9...

Страница 18: ...riod set in P2 20 P2 21 Display Scaling Factor 0 000 to 30 000 0 000 Disabled if P2 21 is set to 0 If P2 21 is set 0 the variable selected in P2 22 is multiplied by the factor entered in P2 21 and dis...

Страница 19: ...ts an offset as a percentage of the full scale range of the input which is applied to the analog input signal P2 33 2 nd analog input format Digital 0 to 10V DC 4 to 20mA 0 to 20mA Selects the format...

Страница 20: ...ference Setpoint 0 P3 06 is used 1 Bipolar analog input is used P3 06 PID digital reference 0 0 to 100 0 0 0 Sets the preset digital PID reference setpoint P3 07 PID controller high limit output P3 08...

Страница 21: ...s Phase to phase supply voltage P0 23 Supply voltage L2 L3 Drive dependent Volts Phase to phase supply voltage P0 24 Supply voltage L3 L1 Drive dependent Volts Phase to phase supply voltage P0 25 Rese...

Страница 22: ...osed Reverse Run enable External trip input Open Trip Closed No Trip Bipolar analog input 11 Open Stop disable Closed Run enable Open Bipolar analog speed ref Closed Preset speed 1 External trip input...

Страница 23: ...ut 18 Open Stop disable Closed Run enable Open Digital speed ref Closed Preset speed ref Digital Input 3 Bipolar analog input Preset reference Open Open Preset Speed 1 Closed Open Preset Speed 2 Open...

Страница 24: ...s Control Mode P1 12 4 P2 01 Digital input 1 T2 Digital input 2 T3 Digital input 3 Analog input 2 T4 Bipolar analog input T6 0 2 4 6 9 13 16 18 Open Stop disable Closed Run enable No Function No Funct...

Страница 25: ...rcuit Check drive ambient temp additional space or cooling needed Check drive is not forced into overload Over voltage on DC bus Supply problem or increase decel ramp time P1 04 Under voltage on DC bu...

Страница 26: ...100 6 ODV 42185 9 ODV 42250 USA 12 4 96 1 100 25 36 39 6 10 100 6 ODV 42220 11 ODV 42300 USA 15 4 115 4 125 35 45 49 5 16 100 6 ODV 52300 15 ODV 52400 USA 20 5 146 1 160 50 55 60 5 16 100 3 ODV 52370...

Страница 27: ...L applications NOTE For cUL compliance fuse type Bussmann KTN R KTS R or equivalent must be used ODV 34150 ODV 34200 USA units are not UL listed 380 480V 10 3 Phase Input 3 Phase Output Model kW Model...

Страница 28: ...050 USA 5 2 7 6 10 1 5 6 1 6 7 1 5 100 47 ODV 25550 5 5 ODV 25075 USA 7 5 2 11 7 16 2 5 9 9 9 2 5 100 47 ODV 35075 7 5 ODV 35100 USA 10 3 16 1 20 2 5 14 15 4 2 5 100 22 ODV 35110 11 ODV 35150 USA 15 3...

Страница 29: ...ands Many Master devices treat the first Register address as Register 0 therefore it may be necessary to convert the Register Numbers detail in section 10 5 by subtracting 1 to obtain the correct Regi...

Страница 30: ...R 03 Output Motor Current 0 6000 Output Motor Current in Amps x10 e g 10 1 0 Amps 10 R 03 Output Motor Power 0 3200 Output Motor Power in kW x10 e g 100 10 0kW 11 R 03 Digital input status 0 15 Indic...

Страница 31: ...tion Units Default User Setting P2 34 2 nd analog input scaling 100 0 P2 01 Digital input function select 0 P2 35 Digital speed reference scaling control 0 P2 02 Preset Speed 2 Hz 0 0 P2 36 Analog out...

Страница 32: ...26 Keypad operation see page 14 Motor Cable Sizes Check drive rating information on page 26 Motor Connections Check for Star or Delta see page 10 Motor Nameplate Details Enter the motor rated voltage...

Отзывы: