Optidrive VTC – User Guide 

 

                                                      www.invertek.co.uk 

 

 

 

17

 

6.2.

 

Parameter Group 2 - Extended parameters 

Par. 

Description 

Range 

Units 

Default 

Explanation 

P2-01 

Digital input function 
select 

0 to 23 

Defines the function of the digital inputs 
depending on the control mode setting in P-12.  
See section 7 Analog and Digital Input 
Configurations for more information. 

P2-02 

Preset Speed 2 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog / preset speed 2 

P2-03 

Preset Speed 3 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog / preset speed 3 

P2-04 

Preset Speed 4 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog / preset speed 4 

P2-05 

Preset Speed 5 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog /preset speed 5 

P2-06 

Preset Speed 6 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog / preset speed 6 

P2-07 

Preset speed 7 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog / preset speed 7 

P2-08 

Preset speed 8 

-P1-01  to  P1-01 

Hz 

0.0 

Sets jog / preset speed 8 

P2-09 

Skip frequency 

P1-02  to  P1-01 

Hz 

0.0 

Centre point of skip frequency band set up in 
conjunction with P2-10 

P2-10 

Skip frequency band 

0 to P1-01 

Hz 

0.0 

Width of skip frequency band centred on 
frequency set in P2-09 

P2-11 

Analog output /  
Digital Output 1 
Function select 

Digital output mode 

0 : Drive enabled 
1 : Drive healthy 
2 : Motor at target speed 
3 : Motor Speed > 0 
4 : Motor speed >= limit 
5 : Motor  current >= limit 
6 : 2

nd

 Analog Input >= limit 

 

Analog Output Mode 

7 : Motor speed 
8 : Motor Current 
9 : Motor power 

 

Digital Output Mode. Logic 1 = +24V DC  
0 : Logic 1 when the drive is enabled (Running) 
1: Logic 1 When no Fault condition exists on the 
drive 
2 : Logic 1 when the motor speed matches the 
setpoint speed 
3 : Logic 1 when the motor runs above zero 
speed 
Options 4 to 6 : the Digital output is enabled 
using the level set in P2-12h and P2-12L 
Analog Output Mode 
7 : Motor Speed, 0 to 10V = 0 to P-01 
8 : Motor Current, 0 to 10V = 0 to 200% of P1-
08 
9 : Motor power, 0 to 10V = 0 to 150% of drive 
rated power 
10 :  

P2-12h 

Digital Output Control 
High Limit 

0.0  to  200.0 

100.0 

With P2-11 = 4 to 6, Digital Output 1 is set to 
Logic 1 (+24V DC) when the value set in P2-12h 
is exceeded, and returns to Logic 0 (0V) when 
the selected value reduces below the limit set 
in P2-12L 

P2-12L 

Digital Output Control 
Low Limit 

0.0 to P2-12h 

100.0 

P2-13 

User Relay Output 
Function Select 

0 : Drive enabled 
1 : Drive healthy 
2 : Motor at target speed 
3 : Motor Speed >0 
4 : Motor speed >= limit 
5 : Motor  current >= limit 
6 : 2

nd

 Analog Input >= limit 

 

Selects the function assigned to the relay 
output. 
0 : Logic 1 when the drive is enabled (Running) 
1 : Logic 1 When no Fault condition exists on 
the drive 
2 : Logic 1 when the motor speed matches the 
setpoint speed 
3 : Logic 1 when the motor runs above zero 
speed 
Options 4 to 6 : the Digital output is enabled 
using the level set in P2-14h and P2-14L 

P2-14h 

Relay Output Control 
High Limit  

0.0  to  200.0 

100.0 

With P2-13 = 4 to 6, the User Relay Output is 
set to Logic 1 (+24V DC) when the value set in 
P2-14h is exceeded, and returns to Logic 0 (0V) 
when the selected value reduces below the 
limit set in P2-12L 

P2-14L 

Relay Output Control 
Low Limit 

0.0 to P2-14h 

100.0 

P2-15 

Relay Output Mode 

0 : Normally Open 
1 : Normally Closed 

Inverts the operating status of the User Relay 
0 : Logic 1 = Relay Contacts Closed 
1 : Logic 1 = Relay Contacts Open 
The drive must be powered for the contacts to 
close 

P2-16 

Standby Mode Wake Up 
Speed  

0.0 to 100.0 

0.0 

Drive will wake from Standby Mode if the 
setpoint exceeds this value 

Содержание Optidrive VTC

Страница 1: ...User Guide Optidrive VTC Variable Torque Control AC Variable Speed Drive 1 5 160kW 2 250HP Installation and operating instructions...

Страница 2: ...ired Use screened motor cable Note For motor cable lengths greater than 100m an output dv dt filter must be used part number OD OUTFx please refer to the Invertek Stock Drives Catalogue for further de...

Страница 3: ...tings 13 5 5 Terminal Control 14 5 6 Keypad Control 14 5 7 Motor Autotuning 15 5 8 Operation of Three Phase drives on Single Phase Supplies 15 6 PARAMETERS 16 6 1 Parameter Group 1 Basic Parameters 16...

Страница 4: ...he enable input signal is present The STOP function does not remove potentially lethal high voltages ISOLATE the drive and wait 10 minutes before starting any work on it Electric shock hazard Disconne...

Страница 5: ...V 10 3 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size ODV3 22150 xx 1 5 ODV3 22020 USA 2 7 2 ODV3 22220 xx 2 2 ODV3 22030 USA 3 10 5 9 2 ODV 32030 xx 3 0 ODV 32040 USA 4...

Страница 6: ...ht 260mm Width 171mm Depth 175mm A 210mm B 163mm Incoming Power Terminals C 25mm Help Card Keypad Display See Section 0 on page 12 Footprint View RJ11 Connector See Section Infra Red Interface Weight...

Страница 7: ...s N1 160mm Centres N2 105mm Slots D1 8 5 x 22mm Busbar Connections Length A1 40mm Connection Diameter D2 9mm Note The choke is always supplied with the drive and MUST be used 3 2 Before Installation C...

Страница 8: ...water from all directions High moisture salt or chemical content environments should use a suitably sealed non vented enclosure Enclosure Front View Enclosure Side View The enclosure design and layou...

Страница 9: ...unding point for the motor cable shield The motor cable shield connected to this terminal drive end should also be connected to the motor frame motor end Use a shield terminating or EMI clamp to conne...

Страница 10: ...r Terminal Box Connections Most general purpose motors are wound for operation on dual voltage supplies this is indicated on the nameplate of the motor This operational voltage is normally selected wh...

Страница 11: ...tput 4 Digital Input 3 Analog Input 2 Digital Logic 1 input voltage range 8 to 30V DC Logic 0 input voltage range 0 to 8 V DC Analog 0 to 10V 0 to 20mA or 4 to 20mA 5 24V User Output 24V 100mA 1k mini...

Страница 12: ...n parameter edit mode RESET STOP Used to reset a tripped drive When in Keypad mode is used to Stop a running drive START When in keypad mode used to Start a stopped drive or to reverse the direction o...

Страница 13: ...isplay shows Press Display shows Set Parameter to minimum value Any numerical value Whilst editing a parameter value The parameter is set to the minimum value When editing P1 01 Display shows Press Di...

Страница 14: ...be adjusted anywhere between minimum and maximum speed using the potentiometer To display motor current Amps briefly press the Navigate key Press again to display the motor power Press again to retur...

Страница 15: ...trol mode is changed P4 01 User Selected Autotune The user can program the drive to carry an autotune if required as follows Ensure the motor nameplate values are correctly entered in P1 07 Motor Rate...

Страница 16: ...el ramp time P1 06 Energy Optimiser 0 Disabled 1 Enabled 0 Disabled When enabled automatically reduces applied motor voltage on light load Minimum value is 50 of nominal P1 07 Motor rated voltage 0 20...

Страница 17: ...above zero speed Options 4 to 6 the Digital output is enabled using the level set in P2 12h and P2 12L Analog Output Mode 7 Motor Speed 0 to 10V 0 to P 01 8 Motor Current 0 to 10V 0 to 200 of P1 08 9...

Страница 18: ...riod set in P2 20 P2 21 Display Scaling Factor 0 000 to 30 000 0 000 Disabled if P2 21 is set to 0 If P2 21 is set 0 the variable selected in P2 22 is multiplied by the factor entered in P2 21 and dis...

Страница 19: ...ts an offset as a percentage of the full scale range of the input which is applied to the analog input signal P2 33 2 nd analog input format Digital 0 to 10V DC 4 to 20mA 0 to 20mA Selects the format...

Страница 20: ...ference Setpoint 0 P3 06 is used 1 Bipolar analog input is used P3 06 PID digital reference 0 0 to 100 0 0 0 Sets the preset digital PID reference setpoint P3 07 PID controller high limit output P3 08...

Страница 21: ...s Phase to phase supply voltage P0 23 Supply voltage L2 L3 Drive dependent Volts Phase to phase supply voltage P0 24 Supply voltage L3 L1 Drive dependent Volts Phase to phase supply voltage P0 25 Rese...

Страница 22: ...osed Reverse Run enable External trip input Open Trip Closed No Trip Bipolar analog input 11 Open Stop disable Closed Run enable Open Bipolar analog speed ref Closed Preset speed 1 External trip input...

Страница 23: ...ut 18 Open Stop disable Closed Run enable Open Digital speed ref Closed Preset speed ref Digital Input 3 Bipolar analog input Preset reference Open Open Preset Speed 1 Closed Open Preset Speed 2 Open...

Страница 24: ...s Control Mode P1 12 4 P2 01 Digital input 1 T2 Digital input 2 T3 Digital input 3 Analog input 2 T4 Bipolar analog input T6 0 2 4 6 9 13 16 18 Open Stop disable Closed Run enable No Function No Funct...

Страница 25: ...rcuit Check drive ambient temp additional space or cooling needed Check drive is not forced into overload Over voltage on DC bus Supply problem or increase decel ramp time P1 04 Under voltage on DC bu...

Страница 26: ...100 6 ODV 42185 9 ODV 42250 USA 12 4 96 1 100 25 36 39 6 10 100 6 ODV 42220 11 ODV 42300 USA 15 4 115 4 125 35 45 49 5 16 100 6 ODV 52300 15 ODV 52400 USA 20 5 146 1 160 50 55 60 5 16 100 3 ODV 52370...

Страница 27: ...L applications NOTE For cUL compliance fuse type Bussmann KTN R KTS R or equivalent must be used ODV 34150 ODV 34200 USA units are not UL listed 380 480V 10 3 Phase Input 3 Phase Output Model kW Model...

Страница 28: ...050 USA 5 2 7 6 10 1 5 6 1 6 7 1 5 100 47 ODV 25550 5 5 ODV 25075 USA 7 5 2 11 7 16 2 5 9 9 9 2 5 100 47 ODV 35075 7 5 ODV 35100 USA 10 3 16 1 20 2 5 14 15 4 2 5 100 22 ODV 35110 11 ODV 35150 USA 15 3...

Страница 29: ...ands Many Master devices treat the first Register address as Register 0 therefore it may be necessary to convert the Register Numbers detail in section 10 5 by subtracting 1 to obtain the correct Regi...

Страница 30: ...R 03 Output Motor Current 0 6000 Output Motor Current in Amps x10 e g 10 1 0 Amps 10 R 03 Output Motor Power 0 3200 Output Motor Power in kW x10 e g 100 10 0kW 11 R 03 Digital input status 0 15 Indic...

Страница 31: ...tion Units Default User Setting P2 34 2 nd analog input scaling 100 0 P2 01 Digital input function select 0 P2 35 Digital speed reference scaling control 0 P2 02 Preset Speed 2 Hz 0 0 P2 36 Analog out...

Страница 32: ...26 Keypad operation see page 14 Motor Cable Sizes Check drive rating information on page 26 Motor Connections Check for Star or Delta see page 10 Motor Nameplate Details Enter the motor rated voltage...

Отзывы: