Optidrive VTC – User Guide
www.invertek.co.uk
21
6.5.
Parameter Group 0 – Monitoring Parameters (Read Only)
Par.
Description
Display range
Units
Explanation
P0-01
Bipolar analog input value
-100.0 to 100.0
%
100% = max input voltage
P0-02
2nd Analog input value
0.0 to 100.0
%
100% = max input voltage
P0-03
Speed controller reference
-500.0 to 500.0
%
100% = P1-09
P0-04
Digital speed reference
-P1-01 to P1-01
Hz / Rpm
Digital speed reference
P0-05
Reserved
P0-06
PID Reference
0.0 to 100.0
%
PID reference / setpoint
P0-07
PID Feedback
0.0 to 100.0
%
PID controller feedback value
P0-08
PID error
0.0 to 100.0
%
Actual PID error
P0-09
PID P Term
0.0 to 100.0
%
Proportional component
P0-10
PID I term
0.0 to 100.0
%
Integral component
P0-11
PID D term
0.0 to 100.0
%
Differential component
P0-12
PID Output
0.0 to 100.0
%
Output from PID controller
P0-13
Motor Voltage
Rating Dependent
V
Output Voltage
P0-14
Magnetising current
Drive dependent
A
Motor rms magnetising current
P0-15
Reserved
P0-16
Field Strength
0.0 to 100.0
%
Magnetic field strength
P0-17
Stator resistance
Drive dependent
Ohms
Phase to phase stator resistance
P0-18
Reserved
P0-19
Reserved
P0-20
DC Bus Voltage
0 to 1000
Volts
Internal DC Bus voltage
P0-21
Drive Temperature
0 to 120
ºC
Measured heatsink temperature
P0-22
Supply voltage L1 – L2
Drive dependent
Volts
Phase to phase supply voltage
P0-23
Supply voltage L2 – L3
Drive dependent
Volts
Phase to phase supply voltage
P0-24
Supply voltage L3 – L1
Drive dependent
Volts
Phase to phase supply voltage
P0-25
Reserved
P0-26
kWh meter
0 to 999.9
kWh
Cumulative energy consumption
P0-27
MWh meter
0 to 60,000
MWh
Cumulative energy consumption
P0-28
Software ID – IO Processor
Drive dependent
-
Version number & checksum
P0-29
Software ID – Motor Control
Drive dependent
-
Version number & checksum
P0-30
Drive serial number
Drive dependent
-
Unique drive serial number
6.6.
Fire Mode
Optidrive VTC has an integrated ‘Fire Mode’ function, designed to ensure that the Optidrive can continue to operate without interruption in the
event of a fire. Fire mode disables non-critical trip functions of the Optidrive, so that the Optidrive will continue to operate until either the drive
itself, the motor or the cabling is destroyed by the fire.
Since normal operation of the Optidrive is overridden when fire mode is active, it is possible that damage to the ventilation system may result from
over-pressure. It is also possible that the Optidrive may itself fail or cause damage to the motor.
Invertek Drives Ltd accepts no liability for damage to the Optidrive VTC itself, other components or equipment, HVAC installations, property or
injury to personnel when operated in Fire mode.
In no event shall Invertek Drives Ltd be liable to any party for loss or damage, whether direct or indirect as a result of operating the drive in Fire
Mode.