5.5.

 

Terminal Control 

When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and all parameters have the 
default values as indicated in section 6 Parameters. 
 

 

Connect the drive to the supply, ensuring the correct voltage and fusing / circuit breaker protection – see section 9.2 on page 26. 

 

Connect the motor to the drive, ensuring the correct star/delta connection for the voltage rating - see section 4.6 on page 10. 

 

Enter the motor data from motor nameplate; P1-07 = motor rated voltage, P1-08 = motor rated current, P1-09 = motor rated frequency. 

 

Connect a control switch between the control terminals 1 and 2 ensuring that the contact is open (drive disabled).  

 

Connect a potentiometer (1kΩ min to 10 kΩ max) between terminals 5 and 7, and the wiper to terminal 6. 

 

With the potentiometer set to zero, switch on the supply to the drive. The display will show 



 

Close the control switch, terminals 1-2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the potentiometer. 

 

On first enable from factory default parameters, the Optidrive will carry out an Autotune, and the display shows 



. Leave the 

control switch closed an allow this to complete. 

 

Following completion of the Autotune, the display shows zero speed in Hz (



.

) with the potentiometer turned to minimum. 

 

Turn the potentiometer to maximum. The motor will accelerate to 50Hz, (60Hz for USA drives), the default value of P1-01, under the 

control of the acceleration ramp time P1-03.  The display shows 50Hz (



.

) at max speed.  

 

If the potentiometer is turned to minimum, the motor will decelerate to 0Hz, the default minimum speed set in P1-02, under the control 
of the deceleration ramp P1-04. The output speed can be adjusted anywhere between minimum and maximum speed using the 
potentiometer. 

 

To display motor current (Amps), briefly press the 

 (Navigate) key. 

 

Press 

 again to display the motor power. 

 

Press 

 again to return to speed display. 

 

To stop the motor, disable the drive by opening the control switch (terminals 1-2).  

 

If the enable/disable switch is opened the drive will decelerate to stop at which time the display will show 



5.6.

 

Keypad Control 

To allow the Optidrive to be controlled from the keypad in a forward direction only, set P1-12 =1:  

 

Connect the supply and motor as for terminal control above. 

 

Enable the drive by closing the switch between control terminals 1 & 2. The display will show 



 

Press the 

 key. If this is the first enable from factory default parameters, the drive will carry out an Autotune as described above. On 

completion of the Autotune, the display shows 



.

 

Press 

 to increase speed. 

 

The drive will run forward, increasing speed until 

 is released. 

 

Press  

 to decrease speed. The drive will decrease speed until 

  is released. The rate of deceleration is limited by the setting in 

P1-04 

 

Press the 

 key. The drive will decelerate to rest at the rate set in P1-04. 

 

The display will finally show 



 at which point the drive is disabled 

 

To preset a target speed prior to enable, press the 

 key whilst the drive is stopped. The display will show the target speed, use the 

 & 

 keys to adjust as required then press the 

 key to return the display to 



.  

 

Pressing the 

  key will start the drive accelerating to the target speed. 

 

 

To allow the Optidrive to be controlled from the keypad in a forward and reverse direction, set P1-12 =2:  

 

Operation is the same as when P1-12=1 for start, stop and changing speed. 

 

Press the 

  key. The display changes to 



.

 

Press 

 to increase speed 

 

The drive will run forward, increasing speed until 

 is released. Acceleration is limited by the setting in P1-03. The maximum speed is 

the speed set in P1-01. 

 

To reverse the direction of rotation of the motor, press the 

  key again. 

Содержание Optidrive VTC

Страница 1: ...User Guide Optidrive VTC Variable Torque Control AC Variable Speed Drive 1 5 160kW 2 250HP Installation and operating instructions...

Страница 2: ...ired Use screened motor cable Note For motor cable lengths greater than 100m an output dv dt filter must be used part number OD OUTFx please refer to the Invertek Stock Drives Catalogue for further de...

Страница 3: ...tings 13 5 5 Terminal Control 14 5 6 Keypad Control 14 5 7 Motor Autotuning 15 5 8 Operation of Three Phase drives on Single Phase Supplies 15 6 PARAMETERS 16 6 1 Parameter Group 1 Basic Parameters 16...

Страница 4: ...he enable input signal is present The STOP function does not remove potentially lethal high voltages ISOLATE the drive and wait 10 minutes before starting any work on it Electric shock hazard Disconne...

Страница 5: ...V 10 3 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size ODV3 22150 xx 1 5 ODV3 22020 USA 2 7 2 ODV3 22220 xx 2 2 ODV3 22030 USA 3 10 5 9 2 ODV 32030 xx 3 0 ODV 32040 USA 4...

Страница 6: ...ht 260mm Width 171mm Depth 175mm A 210mm B 163mm Incoming Power Terminals C 25mm Help Card Keypad Display See Section 0 on page 12 Footprint View RJ11 Connector See Section Infra Red Interface Weight...

Страница 7: ...s N1 160mm Centres N2 105mm Slots D1 8 5 x 22mm Busbar Connections Length A1 40mm Connection Diameter D2 9mm Note The choke is always supplied with the drive and MUST be used 3 2 Before Installation C...

Страница 8: ...water from all directions High moisture salt or chemical content environments should use a suitably sealed non vented enclosure Enclosure Front View Enclosure Side View The enclosure design and layou...

Страница 9: ...unding point for the motor cable shield The motor cable shield connected to this terminal drive end should also be connected to the motor frame motor end Use a shield terminating or EMI clamp to conne...

Страница 10: ...r Terminal Box Connections Most general purpose motors are wound for operation on dual voltage supplies this is indicated on the nameplate of the motor This operational voltage is normally selected wh...

Страница 11: ...tput 4 Digital Input 3 Analog Input 2 Digital Logic 1 input voltage range 8 to 30V DC Logic 0 input voltage range 0 to 8 V DC Analog 0 to 10V 0 to 20mA or 4 to 20mA 5 24V User Output 24V 100mA 1k mini...

Страница 12: ...n parameter edit mode RESET STOP Used to reset a tripped drive When in Keypad mode is used to Stop a running drive START When in keypad mode used to Start a stopped drive or to reverse the direction o...

Страница 13: ...isplay shows Press Display shows Set Parameter to minimum value Any numerical value Whilst editing a parameter value The parameter is set to the minimum value When editing P1 01 Display shows Press Di...

Страница 14: ...be adjusted anywhere between minimum and maximum speed using the potentiometer To display motor current Amps briefly press the Navigate key Press again to display the motor power Press again to retur...

Страница 15: ...trol mode is changed P4 01 User Selected Autotune The user can program the drive to carry an autotune if required as follows Ensure the motor nameplate values are correctly entered in P1 07 Motor Rate...

Страница 16: ...el ramp time P1 06 Energy Optimiser 0 Disabled 1 Enabled 0 Disabled When enabled automatically reduces applied motor voltage on light load Minimum value is 50 of nominal P1 07 Motor rated voltage 0 20...

Страница 17: ...above zero speed Options 4 to 6 the Digital output is enabled using the level set in P2 12h and P2 12L Analog Output Mode 7 Motor Speed 0 to 10V 0 to P 01 8 Motor Current 0 to 10V 0 to 200 of P1 08 9...

Страница 18: ...riod set in P2 20 P2 21 Display Scaling Factor 0 000 to 30 000 0 000 Disabled if P2 21 is set to 0 If P2 21 is set 0 the variable selected in P2 22 is multiplied by the factor entered in P2 21 and dis...

Страница 19: ...ts an offset as a percentage of the full scale range of the input which is applied to the analog input signal P2 33 2 nd analog input format Digital 0 to 10V DC 4 to 20mA 0 to 20mA Selects the format...

Страница 20: ...ference Setpoint 0 P3 06 is used 1 Bipolar analog input is used P3 06 PID digital reference 0 0 to 100 0 0 0 Sets the preset digital PID reference setpoint P3 07 PID controller high limit output P3 08...

Страница 21: ...s Phase to phase supply voltage P0 23 Supply voltage L2 L3 Drive dependent Volts Phase to phase supply voltage P0 24 Supply voltage L3 L1 Drive dependent Volts Phase to phase supply voltage P0 25 Rese...

Страница 22: ...osed Reverse Run enable External trip input Open Trip Closed No Trip Bipolar analog input 11 Open Stop disable Closed Run enable Open Bipolar analog speed ref Closed Preset speed 1 External trip input...

Страница 23: ...ut 18 Open Stop disable Closed Run enable Open Digital speed ref Closed Preset speed ref Digital Input 3 Bipolar analog input Preset reference Open Open Preset Speed 1 Closed Open Preset Speed 2 Open...

Страница 24: ...s Control Mode P1 12 4 P2 01 Digital input 1 T2 Digital input 2 T3 Digital input 3 Analog input 2 T4 Bipolar analog input T6 0 2 4 6 9 13 16 18 Open Stop disable Closed Run enable No Function No Funct...

Страница 25: ...rcuit Check drive ambient temp additional space or cooling needed Check drive is not forced into overload Over voltage on DC bus Supply problem or increase decel ramp time P1 04 Under voltage on DC bu...

Страница 26: ...100 6 ODV 42185 9 ODV 42250 USA 12 4 96 1 100 25 36 39 6 10 100 6 ODV 42220 11 ODV 42300 USA 15 4 115 4 125 35 45 49 5 16 100 6 ODV 52300 15 ODV 52400 USA 20 5 146 1 160 50 55 60 5 16 100 3 ODV 52370...

Страница 27: ...L applications NOTE For cUL compliance fuse type Bussmann KTN R KTS R or equivalent must be used ODV 34150 ODV 34200 USA units are not UL listed 380 480V 10 3 Phase Input 3 Phase Output Model kW Model...

Страница 28: ...050 USA 5 2 7 6 10 1 5 6 1 6 7 1 5 100 47 ODV 25550 5 5 ODV 25075 USA 7 5 2 11 7 16 2 5 9 9 9 2 5 100 47 ODV 35075 7 5 ODV 35100 USA 10 3 16 1 20 2 5 14 15 4 2 5 100 22 ODV 35110 11 ODV 35150 USA 15 3...

Страница 29: ...ands Many Master devices treat the first Register address as Register 0 therefore it may be necessary to convert the Register Numbers detail in section 10 5 by subtracting 1 to obtain the correct Regi...

Страница 30: ...R 03 Output Motor Current 0 6000 Output Motor Current in Amps x10 e g 10 1 0 Amps 10 R 03 Output Motor Power 0 3200 Output Motor Power in kW x10 e g 100 10 0kW 11 R 03 Digital input status 0 15 Indic...

Страница 31: ...tion Units Default User Setting P2 34 2 nd analog input scaling 100 0 P2 01 Digital input function select 0 P2 35 Digital speed reference scaling control 0 P2 02 Preset Speed 2 Hz 0 0 P2 36 Analog out...

Страница 32: ...26 Keypad operation see page 14 Motor Cable Sizes Check drive rating information on page 26 Motor Connections Check for Star or Delta see page 10 Motor Nameplate Details Enter the motor rated voltage...

Отзывы: