Optidrive
ODV
‐
2
User
Guide
Revision
1.00
www.invertek.co.uk
29
9.9.
Parameter
Group
0
–
Monitoring
Parameters
(Read
Only)
P0
‐
01
Analog
Input
1
Applied
Signal
Level
Minimum
‐
100.0
Maximum
100.0
Units
%
Default
‐
Displays
the
signal
level
applied
to
analog
input
1
(Terminal
6)
after
scaling
and
offsets
have
been
applied.
P0
‐
02
Analog
Input
2
Applied
Signal
Level
Minimum
0.0
Maximum
100.0
Units
%
Default
‐
Displays
the
signal
level
applied
to
analog
input
2
(Terminal
10)
after
scaling
and
offsets
have
been
applied.
P0
‐
03
Digital
Input
Status
Minimum
00000
Maximum
11111
Units
Binary
Default
‐
Displays
the
status
of
the
drive
inputs,
including
the
extended
I/O
module
(if
fitted).
1
st
Entry:
00000
...
11111.
Drive
digital
Input
status.
MSB
represents
digital
input
1
/
LSB
representing
digital
input
5.
2
nd
Entry:
E
000
...
E
111.
Drive
Extended
(option)
Input
status.
MSB
represents
digital
input
6
/
LSB
representing
digital
input
8.
P0
‐
04
Pre
Ramp
Speed
Controller
Reference
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
‐
Displays
the
set
point
reference
input
applied
to
the
drive
internal
speed
controller
P0
‐
06
Digital
Speed
Reference
(Motorised
Pot)
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
‐
Displays
the
value
of
the
drive
internal
Motorised
Pot
(used
for
keypad)
speed
reference
P0
‐
07
Fieldbus
Communication
Speed
Reference
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
‐
Displays
the
set
‐
point
being
received
by
the
drive
from
the
currently
active
Fieldbus
interface.
P0
‐
08
PID
Reference
(Set
‐
point)
Minimum
0.0
Maximum
100.0
Units
%
Default
‐
Displays
the
set
‐
point
input
to
the
PID
controller.
P0
‐
09
PID
Feedback
Level
Minimum
0.0
Maximum
100.0
Units
%
Default
‐
Displays
the
Feedback
input
signal
to
the
PID
controller
P0
‐
10
PID
Controller
Output
Minimum
0.0
Maximum
100.0
Units
%
Default
‐
Displays
the
output
level
of
the
PID
controller
P0
‐
11
Applied
Motor
Voltage
Minimum
0
Maximum
‐
Units
V
Default
‐
Displays
the
instantaneous
output
voltage
from
the
drive
to
the
motor
P0
‐
12
Cascade
Function
Timer
Minimum
‐
Maximum
‐
Units
Hrs
Default
‐
Run
Time
values
for
variable
speed
and
DOL
pumps
used
in
cascade
function.
5
entry
log.
0
=
Master,
1
=
DOL1,
2
=
DOL2,
3
=
DOL3,
4
=
DOL4
Clocks
can
be
reset
through
P8
‐
20,
Master
Clock
Reset.
P0
‐
13
Trip
History
Log
Minimum
‐
Maximum
‐
Units
%
Default
‐
Displays
the
last
four
fault
codes
for
the
drive.
Refer
to
section
12.1
for
further
information
P0
‐
14
Motor
Magnetising
Current
(Id)
Minimum
‐
Maximum
‐
Units
A
Default
‐
Displays
the
motor
magnetising
Current,
providing
an
auto
tune
has
been
successfully
completed.
P0
‐
16
DC
Bus
Voltage
Ripple
Level
Minimum
‐
Maximum
‐
Units
Vrms
Default
‐
Displays
the
level
of
ripple
present
on
the
DC
Bus
Voltage.
This
parameter
is
used
by
the
Optidrive
for
various
internal
protection
and
monitoring
functions.
P0
‐
17
Motor
Stator
Resistance
(Rs)
Minimum
‐
Maximum
‐
Units
Ohms
Default
‐
Displays
the
measured
motor
stator
resistance,
providing
an
auto
tune
has
been
successfully
completed.
P0
‐
20
DC
Bus
Voltage
Minimum
0
Maximum
1000
Units
Volts
Default
‐
Displays
the
instantaneous
DC
Bus
Voltage
internally
within
the
drive
P0
‐
21
Drive
Temperature
Minimum
0
Maximum
‐
Units
°C
Default
‐
Displays
the
Instantaneous
Heatsink
Temperature
measured
by
the
drive
P0
‐
22
Time
to
Next
Maintenance
Minimum
‐
Maximum
‐
Units
Hours
Default
‐
Displays
the
current
time
period
remaining
before
the
next
maintenance
becomes
due.
Maintenance
interval
is
based
on
the
value
entered
in
P6
‐
24
(Maintenance
Time
Interval)
and
the
elapsed
time
since
the
maintenance
interval
was
enabled
or
reset.
P0
‐
23
Operating
Time
Accumulated
With
Heatsink
Temperature
Above
80°C
Minimum
0
Maximum
‐
Units
HH:MM:SS
Default
‐
Two
entry
display:
First
display
shows
hours.
Second
display
shows
minutes
and
seconds
Displays
the
amount
of
time
in
hours
and
minutes
that
the
Optidrive
has
operated
for
during
its
lifetime
with
a
heatsink
temperature
in
excess
of
80°C.
This
parameter
is
used
by
the
Optidrive
for
various
internal
protection
and
monitoring
functions.