Optidrive
ODV
‐
2
User
Guide
Revision
1.00
www.invertek.co.uk
20
9.
Extended
Parameters
9.1.
Parameter
Group
2
‐
Extended
parameters
P2
‐
01
Preset
Speed
1
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
5.0
Preset
speed
1
is
selected
by
configuring
P1
‐
13
to
an
option
that
permits
logic
selection,
by
using
the
user
defined
logic
configuration
parameters
in
menu
9
(P9
‐
21
to
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
02
Preset
Speed
2
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
10.0
Preset
speed
2
is
selected
by
configuring
P1
‐
13
to
an
option
that
permits
logic
selection,
by
using
the
user
defined
logic
configuration
parameters
in
menu
9
(P9
‐
21to
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
03
Preset
Speed
3
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
25.0
Preset
speed
3
is
selected
using
the
user
defined
logic
configuration
parameters
in
menu
9
(P9
‐
21
–
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
04
Preset
Speed
4
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
50.0
(60.0)
Preset
speed
4
is
selected
using
the
user
defined
logic
configuration
parameters
in
menu
9
(P9
‐
21
–
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
05
Preset
Speed
5
(Pump
Clean
Speed
1)
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
0.0
Preset
speed
5
is
automatically
reference
by
the
clean
function
when
this
function
is
enabled.
See
section
13.5,
Pump
clean
function.
When
clean
function
is
disabled
Preset
speed
5
can
be
selected
as
per
normal
operation
and
is
selected
using
the
user
defined
logic
configuration
parameters
in
menu
9
(P9
‐
21
to
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
06
Preset
Speed
6
(Pump
Clean
Speed
2)
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
0.0
Preset
speed
6
is
automatically
reference
by
the
clean
function
when
this
function
is
enabled.
See
section
13.5,
Pump
clean
function.
When
clean
function
is
disabled
Preset
speed
6
can
be
selected
as
per
normal
operation
and
is
selected
using
the
user
defined
logic
configuration
parameters
in
menu
6
(P9
‐
21
to
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
07
Preset
Speed
7
(Boost
Speed
1
/
Pump
Stir
Speed)
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
0.0
Preset
speed
7
is
automatically
referenced
by
the
start
/
stop
boost
function,
or
the
Pump
Stir
Function,
when
these
functions
are
enabled.
See
section
13.6,
Pump
Stir
function
and
section
14,
PID
control
applications.
When
HVAC
functions
are
disabled
Preset
speed
7
can
be
selected
as
per
normal
operation
and
is
selected
using
the
user
defined
logic
configuration
parameters
in
menu
6
(P9
‐
21
–
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
08
Preset
Speed
8
(Boost
Speed
2)
Minimum
‐
P1
‐
01
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
0.0
Preset
speed
8
is
automatically
reference
by
the
start
/
stop
boost
function
when
this
function
is
enabled.
See
section
14,
PID
control
applications.
When
boost
function
is
disabled
Preset
speed
8
can
be
selected
as
per
normal
operation
(and
is
selected
using
the
user
defined
logic
configuration
parameters
in
menu
6
(P9
‐
21
to
P9
‐
23),
or
selection
configured
through
the
drive
PLC
function
using
the
OptiTools
Studio
Suite
PC
software.
P2
‐
09
Skip
Frequency
Centre
Point
Minimum
P1
‐
02
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
0.0
P2
‐
10
Skip
Frequency
Band
Width
Minimum
0.0
Maximum
P1
‐
01
Units
Hz
/
Rpm
Default
0.0
Note:
The
Skip
Frequency
function
is
used
to
prevent
continuous
operation
of
a
motor
within
a
defined
output
frequency
bandwidth.
Parameter
P2
‐
09
defines
the
centre
point
of
the
skip
frequency
band,
and
is
used
in
conjunction
with
P2
‐
10
to
set
the
bandwidth.
The
Optidrive
output
frequency
will
ramp
through
the
defined
band
at
the
rate
set
in
P1
‐
03
and
P1
‐
04,
but
will
not
maintain
any
output
frequency
within
the
defined
output
band.
Whilst
the
frequency
reference
applied
to
the
drive
is
within
the
band,
the
Optidrive
output
frequency
will
remain
at
the
upper
or
lower
limit
of
the
band
until
a
valid
speed
reference
is
detected.