Optidrive
ODV
‐
2
User
Guide
Revision
1.00
www.invertek.co.uk
24
P2
‐
34
Analog
Input
2
scaling
Minimum
0.0
Maximum
500.0
Units
%
Default
100.0
P2
‐
34
is
used
to
scale
the
analog
input
prior
to
being
applied
as
a
reference
to
the
drive.
For
example,
if
P2
‐
34
is
set
for
0
–
10V,
and
the
scaling
factor
is
set
to
200.0%,
a
5
volt
input
will
result
in
the
drive
running
at
maximum
speed
(P1
‐
01)
P2
‐
35
Analog
Input
2
Offset
Minimum
‐
500.0
Maximum
500.0
Units
%
Default
0.0
P2
‐
35
defines
an
offset
for
the
analog
input,
as
a
percentage
of
the
full
range
of
the
input.
A
positive
offset
is
deducted
from
the
incoming
analog
signal
and
a
negative
offset
is
added
to
the
signal.
For
example,
if
P2
‐
33
is
set
for
0
–
10V,
and
the
analog
offset
is
set
to
10.0%,
then
1
volt
(10%
of
10V)
will
be
deducted
from
the
incoming
analog
reference
prior
to
it
being
applied.
P2
‐
36
Start
Mode
Select
/
Automatic
Restart
Minimum
‐
Maximum
‐
Units
‐
Default
Auto-0
Defines
the
behaviour
of
the
drive
relating
to
the
enable
digital
input
and
also
configures
the
Automatic
Restart
function.
Edge-r
:
Following
Power
on
or
reset,
the
drive
will
not
start
if
Digital
Input
1
remains
closed.
The
Input
must
be
closed
after
a
power
on
or
reset
to
start
the
drive.
Auto-0
:
Following
a
Power
On
or
Reset,
the
drive
will
automatically
start
if
Digital
Input
1
is
closed.
Auto-1
to
Auto-5
:
Following
a
trip,
the
drive
will
make
up
to
5
attempts
to
restart
at
20
second
intervals.
The
drive
must
be
powered
down
to
reset
the
counter
.
The
numbers
of
restart
attempts
are
counted,
and
if
the
drive
fails
to
start
on
the
final
attempt
the
drive
will
trip
with
the
fault
and
will
require
the
user
to
manually
reset
the
drive.
P2
‐
37
Keypad
Mode
Restart
Speed
Minimum
0
Maximum
3
Units
‐
Default
1
This
parameter
is
only
active
when
P1
‐
12
=
1
or
2
(keypad
Mode)
0
:
Minimum
Speed
.
Following
a
stop
and
restart,
the
drive
will
always
initially
run
at
the
minimum
speed
P1
‐
02
1
:
Previous
Operating
Speed
.
Following
a
stop
and
restart,
the
drive
will
return
to
the
last
keypad
set
‐
point
speed
used
prior
to
stopping
2
:
Current
Running
Speed
.
Where
the
Optidrive
is
configured
for
multiple
speed
references
(typically
Hand
/
Auto
control
or
Local
/
Remote
control),
when
switched
to
keypad
mode
by
a
digital
input,
the
drive
will
continue
to
operate
at
the
last
operating
speed
3
:
Preset
Speed
4
.
Following
a
stop
and
restart,
the
Optidrive
will
always
initially
run
at
Preset
Speed
4
(P2
‐
04)
P2
‐
38
Mains
Loss
Ride
Through
/
Stop
Function
Minimum
0
Maximum
2
Units
‐
Default
0
Controls
the
behaviour
of
the
drive
in
response
to
a
loss
of
mains
power
supply
whilst
the
drive
is
enabled.
0:
Mains
Loss
Ride
Through
.
The
Optidrive
will
attempt
to
continue
operating
by
recovering
energy
from
the
load
motor.
Providing
that
the
mains
loss
period
is
short,
and
sufficient
energy
can
be
recovered
before
the
drive
control
electronics
power
off,
the
drive
will
automatically
restart
on
return
of
mains
power
1:
Coast
To
Stop
.
The
Optidrive
will
immediately
disable
the
output
to
the
motor,
allowing
the
load
to
coast
or
free
wheel.
When
using
this
setting
with
high
inertia
loads,
the
Spin
Start
function
(P2
‐
26)
may
need
to
be
enabled
2:
Fast
Ramp
To
Stop
.
The
drive
will
ramp
to
stop
at
the
rate
programmed
in
the
Fast
deceleration
time
P2
‐
25
P2
‐
39
Parameter
Access
Lock
Minimum
0
Maximum
1
Units
‐
Default
0
0
:
Unlocked
.
All
parameters
can
be
accessed
and
changed
1
:
Locked
.
Parameter
values
can
be
displayed,
but
cannot
be
changed
P2
‐
40
Extended
Parameter
Access
Code
Definition
Minimum
0
Maximum
9999
Units
‐
Default
101
Defines
the
access
code
which
must
be
entered
in
P1
‐
14
to
access
parameter
groups
above
Group
1