Optidrive
ODV
‐
2
User
Guide
Revision
1.00
www.invertek.co.uk
28
P8
‐
11
Bypass
Mode
on
Fault
(Enable)
Minimum
0
Maximum
1
Units
‐
Default
0
Parameter
configures
the
drive
to
switch
to
bypass
mode
automatically
should
a
trip
occur
on
the
drive.
When
enabled
the
drive
standard
relays
1
and
2
are
dedicated
to
bypass
control
and
cannot
be
assigned
other
functions.
0
=
Disabled
1
=
Enabled
P8
‐
12
Bypass
mode
of
Fire
Enable
Minimum
0
Maximum
1
Units
‐
Default
0
Parameter
configures
the
drive
to
switch
to
bypass
mode
automatically
should
an
input
to
the
drive
be
configured
for
Fire
Mode
operation
and
that
input
becomes
active.
When
enabled
the
drive
standard
relays
1
and
2
are
dedicated
to
bypass
control
and
cannot
be
assigned
other
functions.
0
=
Disabled
1
=
Enabled
P8
‐
13
Bypass
Contactor
Changeover
Time
Minimum
0
Maximum
30
Units
Secs
Default
2
Parameter
active
when
Bypass
function
is
enabled.
Parameter
P8
‐
05
sets
a
time
delay
or
changeover
time
between
the
switching
of
the
drive
relays
controlling
the
bypass
circuitry.
Care
must
be
taken
when
setting
P8
‐
13
to
ensure
that
drive
and
DOL
contactors
are
not
switched
in
circuit
simultaneously.
Both
Mechanical
and
Electrical
interlocking
of
drive
and
DOL
contactors
to
regional
standards
are
recommended
in
configuring
the
Bypass
function.
Note:
For
full
detail
on
the
Bypass
Mode
function
see
section
13.7,
Bypass
Control
Function,
or
contact
your
local
Invertek
distributor
P8
‐
14
Pump
Staging
Function
Select
Minimum
0
Maximum
2
Units
‐
Default
0
Parameter
enables
the
pump
staging
(cascade)
function
on
the
drive
0
=
Disabled
1
=
Single
VFD
with
DOL
Cascade
(max
4
DOL
pumps)
2
=
Multiple
Drive
Cascade
Master
Drive
(Only
valid
when
drive
set
to
Optibus
master
address,
P5
‐
01
=
1)
P8
‐
15
Pump
Staging
DOL
Pump
Availability
Minimum
0
Maximum
4
Units
‐
Default
0
Parameter
valid
when
P8
‐
14
is
set
to
1
or
2
to
enable
Pump
Staging
Function.
P8
‐
15
set
the
number
of
DOL
pumps
(P8
‐
14
=
1)
or
network
slave
drives
(P8
‐
14
=
2)
that
are
available
in
the
Pump
Staging
application.
Setting
the
value
to
0
disables
Pump
Staging.
P8
‐
16
Pump
Staging
Duty
Switch
Over
Time
Minimum
0
Maximum
1000
Units
Hours
Default
0
In
order
to
balance
run
time
(duty)
on
each
pump
in
the
Pump
staging
application
and
to
ensure
periodic
operation
of
each
pump
P8
‐
16
can
be
set
with
a
time
limit
for
pump
switch
over.
When
set
to
a
value
other
than
0
(disabled)
the
operation
of
each
staging
pump
will
be
cycled
to
ensure
the
difference
in
duty
between
each
pump
does
not
exceed
the
time
set
in
P8
‐
16
P8
‐
17
Pump
Staging
Switch
In
Speed
Minimum
P8
‐
18
Maximum
P1
‐
01
Units
Hz
/
RPM
Default
0
HVAC
Optidrive
upper
speed
Staging
threshold.
When
the
drive
output
increases
beyond
this
threshold
the
next
Staging
pump
is
switch
on.
The
Pump
staging
settle
time
must
then
expire
before
additional
staging
pumps
can
be
brought
on
or
off
line.
Priority
for
Staging
pump
switch
on
is
always
given
to
the
pump
with
lowest
run
time
accumulated.
P8
‐
18
Pump
Staging
Switch
Out
Speed
Minimum
0
Maximum
P8
‐
17
Units
Hz
/
RPM
Default
0
HVAC
Optidrive
lower
speed
Staging
threshold.
When
the
drive
output
decreases
below
this
threshold
one
of
the
Staging
pumps
currently
operating
is
switch
off.
The
Pump
staging
settle
time
must
then
expire
before
additional
staging
pumps
can
be
brought
on
or
off
line.
Priority
for
Staging
pump
switch
off
is
always
given
to
the
pump
with
highest
run
time
accumulated.
P8
‐
19
Pump
Staging
System
Settle
Time
Minimum
10
Maximum
600
Units
Secs
Default
10
Parameter
sets
a
time
delay
for
pump
staging
whereby,
following
switch
in
or
switch
out
of
a
staging
pump,
further
pumps
are
not
permitted
to
be
switched
in
or
out
until
this
time
period
has
elapsed.
This
parameter
should
be
set
to
allow
adequate
settle
time
between
staging
pump
transitions.
P8
‐
20
Pump
Staging
Master
Clock
Reset
Minimum
0
Maximum
1
Units
‐
Default
0
Master
drive
in
pump
staging
monitors
and
maintains
duty
run
times
for
all
available
staging
pumps.
All
clocks
are
available
to
view
in
P0
‐
20.
P8
‐
20
provides
the
master
reset
to
all
run
time
clocks
used
for
Pump
Staging
Function
(all
clocks
set
to
0).
Note:
For
full
detail
of
Pump
Staging
function
configuration
see
section
13.1
and
13.2,
or
contact
your
local
Invertek
distributor
9.8.
Parameter
Group
9
–
Advance
drive
control
logic
configuration
Menu
group
9
parameters
are
detailed
in
the
advanced
user
guide.
They
can
be
accessed
through
the
drive
keypad
by
setting
advanced
security
level
access
(P1
‐
14
=
201)
or
through
the
OptiTools
Studio
software
suite.