Optidrive ODP-2ETHEG-IN User Guide Revisions 1.00 

 

www.invertekdrives.com 

13

 

 

6

 
O

p

e

ra

ti

o

n

 

6.6.

 

Process Data PDO 

PDO data is returned from the drive to the master PLC. The available data for each word is described below. 

6.6.1.

 

PDO Word 1: Drive Status Word 

The function of PDO Word 1 is fixed for all drive models, and returns the drive Status Word. The individual bits within the drive status word 
indicates the status of the drive as follows. Some functions are applicable to specific drive types, as indicated below. 

Bit 

Function 

E3 

P2 

Eco 

0 = Drive Disabled (Stopped) 
1 = Drive Enabled (Running) 

 

 

 

0 = Drive Healthy 
1 = Drive Tripped 

 

 

 

0 = Auto 
1 = Hand 

 

 

 

0 = Drive Ready (STO Input Closed) 
1 = Drive Inhibit (STO Input Option 

 

 

 

0 = Maintenance Time Not Reached 
1 = Maintenance Time Reached 

 

 

 

0 = Not In Standby (Sleep) 
1 = Standby (Sleep) mode active 

 

 

 

0 = Not Ready 
1 = Drive Ready (Mains Power applied, No Inhibit, No Trip, Enable Input Present) 

 

 

 

0 = No Warning 
1 = Motor Load Current Outside bandwidth 

 

 

 

8 - 15 

Fault code number. Refer to the table in section 0 

 

 

 

 

6.6.2.

 

Drive Fault Codes 

The following table provides a list of the possible fault code numbers returned in the Drive Stratus Word High Byte, and the relevant fault 
information for each code. Refer to the relevant drive User Guide for further information on the cause and possible solutions for each fault. 
 

No. 

Fault Description 

00 

No Fault 

01 

Brake channel over current 

02 

Brake resistor overload 

03 

Instantaneous over current on drive output.  
Excess load on the motor. 

04 

Drive has tripped on overload after delivering >100% of value in P1-08 for a period of time. 

05 

Hardware Over Current  

06 

Over voltage on DC bus 

07 

Under voltage on DC bus 

08 

Heatsink over temperature 

09 

Under temperature 

10 

Factory Default parameters have been loaded 

11 

External trip 

12 

Communications Fault 

13 

Excessive DC Ripple 

14 

Input phase loss trip 

15 

Instantaneous over current on drive output. 

16 

Faulty thermistor on heatsink. 

17 

Internal memory fault. 

18 

4-20mA Signal Lost 

19 

Internal memory fault. 

20 

User Parameter Defaults 

21 

Motor PTC Over Temperature 

22 

Cooling Fan Fault 

23 

Ambient Temperature too High 

24 

Maximum Torque Limit Exceeded 

25 

Output Torque Too Low 

26 

Drive output fault 

29 

Internal STO circuit Error  

30 

Encoder Feedback Fault 

31 

Speed Error 

32 

Encoder Feedback Fault 

33 

Encoder Feedback Fault 

34 

Encoder Feedback Fault 

35 

Encoder Feedback Fault 

40 

Autotune Failed 

41 
42 
43 
44 
45 

Input phase sequence incorrect 

49 

Output (Motor) Phase Loss 

50 

Modbus comms fault 

51 

CAN Open comms trip 

52 

Communications Option Module Fault 

53 

IO card comms trip 

 

Содержание OPT-2-ETHEG-IN

Страница 1: ...OPT 2 ETHEG IN Ethernet IP Interface Installation and Operating Instructions Installation Operating Instructions...

Страница 2: ...on 8 4 1 Overview 8 4 2 Connection Diagram 8 4 3 Grounding 8 5 Drive Parameter Settings 9 5 1 Overview 9 5 2 Optidrive Communication Parameters Overview 9 6 Operation 11 6 1 Overview 11 6 2 Configurat...

Страница 3: ...transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation inco...

Страница 4: ...achinery Directive 2006 42 EC Safety of Machinery In particular the machine manufacturer is responsible for ensuring that the electrical equipment complies with EN60204 1 and providing a disconnecting...

Страница 5: ...and PR ID Data for the module Side Label Provides the model code and serial number data 2 3 Connection Ports The interface connects to the Ethernet IP network and slave drive via the built in connecti...

Страница 6: ...active Steady flashing Yellow Modbus protocol TX RX active ERROR State Indication Steady Off Modbus protocol TX RX Status OK Steady Red Non recoverable internal fault Modbus communications circuit fau...

Страница 7: ...C 3 2 General The Ethernet IP interface is intended for mounting inside a control cabinet adjacent to the drive The unit should be mounted in a vertical position only on a flat flame resistant vibrati...

Страница 8: ...onnects via an RJ45 cable which also supplies the power to the OPT 2 ETHEG IN from the 24 Volt output of the Optidrive 4 2 Connection Diagram Optional Drive Keypad OPT 2 OPORT IN OPT 2 OPPAD IN RJ45 C...

Страница 9: ...signal must still be provided at the control terminals digital input 1 P 14 Extended Menu Access code 0 65535 0 Enables access to Extended and Advanced Parameter Groups This parameter must be set to...

Страница 10: ...status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C P5 12 Fieldbus Process Data Output Word 3 Select...

Страница 11: ...3 address 1 For Drive specific allocation refer to Drive Manual and or Ethernet IP EDS file For Drive specific read write limitations refer to Drive Manual and or Ethernet IP EDS file The following c...

Страница 12: ...No Function 1 Fault Reset Request 3 0 Normal Operation 1 Coast Stop 4 No function 5 6 7 6 5 2 PDI Word 2 Drive Speed Reference The drive speed reference value has one decimal place e g commanded valu...

Страница 13: ...information for each code Refer to the relevant drive User Guide for further information on the cause and possible solutions for each fault No Fault Description 00 No Fault 01 Brake channel over curre...

Страница 14: ...Status Displays the status of the drive digital inputs where Bit 0 Digital Input 1 Bit 1 Digital Input 2 etc A bit value of 1 means the input is ON If an external I O module is connected to the drive...

Страница 15: ...xxxxxxx where xxxxxxxxxx PR ID value shown on the top product label as described in section 2 2 Both of the above values can be modified via the Web Server or Ethernet IP Class 0xF4 The Webserver cont...

Страница 16: ...rror status will be displayed Status State Indication Data Submitted Data has been submitted to OPT 2 ETHEG IN awaiting reply Data Read Write Error An error occurred data was not stored Resource Busy...

Страница 17: ...ethods Class Service 0x0F Parameter 0x0E Get_Attribute_Single Individual parameter Read Write Instance 1 holding register 0 0x10 Set_Attribute_Single 0x44 Modbus Object 0x4E Read_Holding_Registers Mul...

Страница 18: ...EDS Hardware Installation Tool 6 9 2 Configure the IP Address Configure the OPT 2 ETHEG IN IP address using either the OPT 2 ETHEG IN Web Server see section 6 7 3 or using RSLinx as follows Launch RS...

Страница 19: ...cal Data 7 1 Environmental Ambient Temperature Storage and Transportation 40 60 C 40 140 F Operating 10 50 C 14 122 F UL Approved 40 50 C 104 122 F Without UL approval Altitude Operating 1000m UL appr...

Страница 20: ...Optidrive ODP 2ETHEG IN User Guide Revisions 1 00 20 www invertekdrives com 7 Technical Data 82 EIPMN IN_V1 00...

Отзывы: