Optidrive E2 Single Phase Output User Guide V3.10

 

 

www.invertekdrives.com 

26

 

 

M

od
b

u

R

TU Co

m

m

u

n

ic

ati

on

8

 

8.

 

Modbus RTU Communications 

8.1.

 

Introduction 

The Optidrive E2 can be connected to a Modbus RTU network via the RJ45 connector on the front of the drive. 

8.2.

 

Modbus RTU Specification 

Protocol 

Modbus RTU 

Error check 

CRC 

Baud rate 

9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 

Data format 

1 start bit, 8 data bits, 1 stop bits, no parity. 

Physical signal 

RS 485 (2-wire) 

User interface 

RJ45 

8.3.

 

RJ45 Connector Configuration 

For full MODBUS RTU register map 

information please refer to your Invertek 

Drives Sales Partner. 

 

When using MODBUS control the Analog and 

Digital Inputs 

can be configured as shown in section 7.3 

 

No Connection 

No Connection 

0 Volts 

-RS485 (PC) 

+RS485 (PC)  

+24 Volt 

-RS485 (Modbus RTU) 

+RS485 (Modbus RTU) 

 

 

 

 

 

 

 

Warning: 

This is not an Ethernet 
connection. Do not connect 
directly to an Ethernet port.

 

 

8.4.

 

Modbus Telegram Structure 

The Optidrive ODE-2 supports Master / Slave Modbus RTU communications, using the 03 Read Holding Registers and 06 Write Single Holding 
Register commands. Many Master devices treat the first Register address as Register 0, therefore it may be necessary to convert the Register 
Numbers detail in section 8.5 by subtracting 1 to obtain the correct Register address. The telegram structure is as follows:- 
 

Command 03 – Read Holding Registers 

 

Command 06 – Write Single Holding Register 

Master Telegram 

Length 

 

Slave Response 

Length 

 

Master Telegram 

Length 

 

Slave Response 

Length 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

Function Code (03) 

1  Byte 

 

Starting Address 

1  Byte 

 

Function Code (06) 

1  Byte 

 

Function Code (06) 

1  Byte 

1

st

 Register Address 

2  Bytes 

 

1

st

 Register Value 

2  Bytes 

 

Register Address 

2  Bytes 

 

Register Address 

2  Bytes 

No. Of Registers 

2  Bytes 

 

2

nd

 Register Value 

2  Bytes 

 

Value 

2  Bytes 

 

Register Value 

2  Bytes 

CRC Checksum 

2  Bytes 

 

Etc... 

 

 

 

CRC Checksum 

2  Bytes 

 

CRC Checksum 

2  Bytes 

 

 

 

 

CRC Checksum 

2  Bytes 

 

 

 

 

 

 

 

 

8.5.

 

Modbus Register Map 

Register 
Number 

Par. 

Type 

Supported 

Commands 

Function 

Range 

Explanation 

Low Byte 

High Byte 

R/W 

03,06 

Drive Control Command 

0..3 

16 Bit Word.  
Bit 0 : Low = Stop, High = Run Enable 
Bit 1 : Low = Decel Ramp 1 (P-04), High = Decel 
Ramp 2 (P-24) 
Bit 2 : Low = No Function, High = Fault Reset 
Bit 3 : Low – No Function, High = Coast Stop 
Request 

R/W 

03,06 

Modbus Speed reference setpoint 

0..5000 

Setpoint frequency x10, e.g. 100 = 10.0Hz 

R/W 

03,06 

Acceleration and Deceleration Time 

0..60000 

Ramp time in seconds x 100, e.g. 250 = 2.5 seconds 

03 

Error code 

Drive status 

 

Low Byte = Drive Error Code, see section 10.1 
High Byte = Drive Status as follows :- 
0 : Drive Stopped 
1: Drive Running 
2: Drive Tripped 

 

03 

Output Motor Frequency 

0..20000 

Output frequency in Hz x10, e.g. 100 = 10.0Hz 

 

03 

Output Motor Current 

0..480 

Output Motor Current in Amps x10, e.g. 10 = 1.0 Amps 

11 

03 

Digital input status 

0..15 

Indicates the status of the 4 digital inputs 
Lowest Bit = 1 Input 1 

20 

P00-01 

03 

Analog Input 1 value 

0..1000 

Analog input % of full scale x10, e.g. 1000 = 100% 

21 

P00-02 

03 

Analog Input 2 value 

0..1000 

Analog input % of full scale x10, e.g. 1000 = 100% 

22 

P00-03 

03 

Speed Reference Value 

0..1000 

Displays the setpoint frequency x10, e.g. 100 = 10.0Hz 

23 

P00-08 

03 

DC bus voltage 

0..1000 

DC Bus Voltage in Volts 

24 

P00-09 

03 

Drive temperature 

0..100 

Drive heatsink temperature in ºC 

All user configurable parameters are accessible as Holding Registers, and can be Read from or Written to using the appropriate Modbus 
command. The Register number for each parameter P-04 to P-047 is defined as 128 + Parameter number, e.g. for parameter P-15, the register 
number is 128 + 15 = 143. Internal scaling is used on some parameters, for further details; please contact your Invertek Drives Sales Partner. 
 

Содержание ODE-2-11005-1H012-01

Страница 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Страница 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Страница 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Страница 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Страница 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Страница 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Страница 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Страница 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Страница 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Страница 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Страница 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Страница 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Страница 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Страница 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Страница 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Страница 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Страница 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Страница 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Страница 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Страница 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Страница 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Страница 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Страница 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Страница 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Страница 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Страница 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Страница 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Страница 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Отзывы: