Optidrive E2 Single Phase Output User Guide V3.10

 

 

www.invertekdrives.com 

18

 

 

Pa
ra

m

e

ter

6

 

6.

 

Parameters 

6.1.

 

Standard Parameters 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-01 

Maximum Frequency / Speed Limit 

P-02 

120.0 

50.0 (60.0) 

Hz / Rpm 

Maximum output frequency or motor speed limit – Hz or rpm. If P-10 >0, the value entered / displayed is in Rpm 

P-02 

Minimum Frequency / Speed Limit 

0.0 

P-01 

0.0 

Hz / Rpm 

Minimum speed limit – Hz or rpm. If P-10 >0, the value entered / displayed is in Rpm 

P-03 

Acceleration Ramp Time 

0.00 

600.0 

5.0 

Acceleration ramp time from 0.0 to base frequency (P-09) in seconds. 

P-04 

Deceleration Ramp Time 

0.00 

600.0 

5.0 

Deceleration ramp time from base frequency (P-09) to standstill in seconds. When set to 0.00, the value of P-24 is used. 

P-05 

Stopping Mode 

0 : Ramp To Stop

. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P-04. If the mains 

supply is lost, the drive will try to continue running by reducing the speed of the load, and using the load as a generator. 

1 : Coast to Stop

. When the enable signal is removed, or if the mains supply is lost, the motor will coast (freewheel) to stop 

2 : Ramp To Stop

. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P-04. If the mains 

supply is lost the drive will ramp to stop using the P-24 Decel ramp with dynamic brake control. 

P-06 

Reserved 

 

P-07 

Motor Rated Voltage 

125 / 250 

115 / 230 

This parameter should be set to the rated (nameplate) voltage of the motor (Volts) 

P-08 

Motor Rated Current 

Drive Rating Dependent 

This parameter should be set to the rated (nameplate) current of the motor 

P-09 

Motor Rated Frequency 

25 

120 

50 (60) 

Hz 

This parameter should be set to the rated (nameplate) frequency of the motor 

P-10 

Motor Rated Speed 

6000 

Rpm 

This parameter can optionally be set to the rated (nameplate) rpm of the motor. When set to the default value of zero, all speed 
related parameters are displayed in Hz, and the slip compensation for the motor is disabled. Entering the value from the motor 
nameplate enables the slip compensation function, and the Optidrive display will now show motor speed in estimated rpm. All speed 
related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in Rpm. 

P-11 

Starting Voltage Boost 

0.0 

100.0 

3.0 

This parameter sets the initial  voltage applied to the motor following a start command. The inverter applied the voltage set in this 
parameter at the frequency set in P-32 initially, and then ramps to the motor rated voltage set in P-09 over the time period set in P-
33. Excessive voltage boost levels may result in increased motor current and temperature, and can result in the drive tripping during 
starting.  
An explanation of the motor starting, and procedure for optimising the boost voltage is described in section 0. 

P-12 

Primary Command Source 

0: Terminal Control

. The drive responds directly to signals applied to the control terminals. 

1 & 2: Uni-directional Keypad Control

.  The drive can be controlled in the forward direction only using an external or remote Keypad  

3: Modbus Network Control. 

Control via Modbus RTU (RS485) using the internal Accel / Decel ramps

 

4 : Modbus Network Control. 

Control via Modbus RTU (RS485) interface with Accel / Decel ramps updated via Modbus

 

5 : PI Control. 

User PI control with external feedback signal

 

6 : PI Analog Summation Control. 

PI control with external feedback signal and summation with analog input 1

 

P-13 

Trip Log History 

N/A 

N/A 

N/A 

N/A 

Previous 4 trips stored in order of occurrence, with the most recent first. Press UP or DOWN to step through all four. The most recent 
trip is always displayed first. UV trip is only stored once. Further fault event logging functions are available through parameter group 
zero. 

P-14 

Extended Menu Access code 

9999 

Set to “101” (default) for extended menu access. Change code in P-37 to prevent unauthorised access to the Extended Parameter Set 

 
 
 

 

 

Содержание ODE-2-11005-1H012-01

Страница 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Страница 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Страница 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Страница 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Страница 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Страница 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Страница 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Страница 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Страница 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Страница 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Страница 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Страница 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Страница 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Страница 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Страница 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Страница 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Страница 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Страница 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Страница 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Страница 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Страница 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Страница 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Страница 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Страница 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Страница 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Страница 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Страница 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Страница 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Отзывы: