Optidrive E2 Single Phase Output User Guide V3.10

 

 

www.invertekdrives.com 

12

 

 

Pow

e

r W

iri

n

4

 

4.

 

Power Wiring 

4.1.

 

Grounding the Drive 

 

This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance or 
the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated equipment. A 
hazard of personal injury and/or equipment damage exists if codes are ignored during installation. 

 

This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before working on 
the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to discharge to safe 
voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life. 

 

Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved 
should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in 
their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. 

Grounding Guidelines 

The ground terminal of each Optidrive should be individually connected DIRECTLY to the site ground bus bar (through the filter if installed). 
Optidrive ground connections should not loop from one drive to another, or to, or from any other equipment. Ground loop impedance must 
confirm to local industrial safety regulations. To meet UL regulations, UL approved ring crimp terminals should be used for all ground wiring 
connections.  
The drive Safety Ground must be connected to system ground. Ground impedance must conform to the requirements of national and local 
industrial safety regulations and/or electrical codes. The integrity of all ground connections should be checked periodically. 
Protective Earth Conductor 
The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor. 

Safety Ground 

This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), 
a floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.  

Motor Ground 

The motor ground must be connected to one of the ground terminals on the drive. 

Ground Fault Monitoring 

As with all inverters, a leakage current to earth can exist. The Optidrive is designed to produce the minimum possible leakage current whilst 
complying with worldwide standards. The level of current is affected by motor cable length and type, the effective switching frequency, the 
earth connections used and the type of RFI filter installed. If an ELCB (Earth Leakage Circuit Breaker) is to be used, the following conditions 
apply: - 

 

A Type B Device must be used 

 

The device must be suitable for protecting equipment with a DC component in the leakage current  

 

Individual ELCBs should be used for each Optidrive 

 
Drives with an EMC filter have an inherently higher leakage current to Ground (Earth).  For applications where tripping occurs the EMC filter 
can be disconnected (on IP20 units only) by removing the EMC screw on the side of the product. 
 

 

 

Remove the screws as indicated below 

 

The Optidrive product range has input supply voltage surge suppression components fitted to protect the drive from line voltage transients, 
typically originating from lightning strikes or switching of high power equipment on the same supply. 
 
When carrying out a HiPot (Flash) test on an installation in which the drive is built, the voltage surge suppression components may cause the 
test to fail.  To accommodate this type of system HiPot test, the voltage surge suppression components can be disconnected by removing the 
VAR screw.  After completing the HiPot test, the screw should be replaced and the HiPot test repeated.  The test should then fail, indicating 
that the voltage surge suppression components are once again in circuit. 
Shield Termination (Cable Screen) 
The safety ground terminal provides a grounding point for the motor cable shield. The motor cable shield connected to this terminal (drive 
end) should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to the safety 
ground terminal. 

4.2.

 

Wiring Precautions 

Connect the Optidrive according to sections 4.7 and 4.8. It is recommended that the power cabling should be 4-core PVC-insulated screened 
cable, laid in accordance with local industrial regulations and codes of practice. 

Remove the 

screws as 

indicated

 

Internal 

EMC 

Filter

 

Internal 

Surge 

Protection

 

EMC

 

VAR

 

Earth

 

Содержание ODE-2-11005-1H012-01

Страница 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Страница 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Страница 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Страница 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Страница 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Страница 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Страница 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Страница 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Страница 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Страница 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Страница 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Страница 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Страница 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Страница 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Страница 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Страница 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Страница 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Страница 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Страница 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Страница 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Страница 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Страница 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Страница 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Страница 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Страница 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Страница 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Страница 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Страница 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Отзывы: