Optidrive E2 Single Phase Output User Guide V3.10 

19 

www.invertekdrives.com 

 

 

Pa

ra

m

e

ter

6

 

6.2.

 

Extended Parameters 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-15 

Digital Input Function Select 

12 

Defines the function of the digital inputs depending on the control mode setting in P-12.  See section 7, Analog and Digital Input 
Configurations for more information. 

P-16 

Analog Input 1 Signal Format 

See Below 

U0-10 



 = 0 to 10 Volt Signal (Uni-polar). The drive will remain at 0.0Hz if the analog reference after scaling and offset are applied is 

<0.0% 



 = Reserved, Not for use with Single phase Output drives

 



 = 0 to 20mA Signal 



 =  4 to 20mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 4 to 20mA Signal, the Optidrive will run at Preset Speed 1 (P-20)  if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will run at Preset Speed 1 (P-20)   if the signal level falls below 3mA 

P-17 

Maximum Effective Switching Frequency 

32 

8 / 16 

kHz 

Sets maximum effective switching frequency of the drive. If “rEd” is displayed, the switching frequency has been reduced to the level in P00-
14 due to excessive drive heatsink temperature.

 

P-18 

Output Relay Function Select 

Selects the function assigned to the relay output. The relay has two output terminals, Logic 1 indicates the relay is active, and 
therefore terminals 10 and 11 will be linked together. 

0

 

: Drive Enabled (Running)

. Logic 1 when the motor is enabled 

1 : Drive Healthy

. Logic 1 when power is applied to the drive and no fault exists 

2

 

: At Target Frequency (Speed)

. Logic 1 when the output frequency matches the setpoint frequency 

3: Drive Tripped

. Logic 1 when the drive is in a fault condition 

4

 

: Output Frequency >= Limit

. Logic 1 when the output frequency exceeds the adjustable limit set in P-19 

5

 

: Output Current >= Limit

. Logic 1 when the motor current exceeds the adjustable limit set in P-19 

6

 

: Output Frequency < Limit

. Logic 1 when the output frequency is below the adjustable limit set in P-19 

7

 

: Output Current < Limit

. Logic 1 when the motor current is below the adjustable limit set in P-19 

P-19 

Relay Threshold Level 

0.0 

200.0 

100.0 

Adjustable threshold level used in conjunction with settings 4 to 7 of P-18 

P-20 

Preset Frequency / Speed 1 

P-02 

P-01 

0.0 

Hz / Rpm 

P-21 

Preset Frequency / Speed 2 

P-02 

P-01 

0.0 

Hz / Rpm 

P-22 

Preset Frequency / Speed 3 

P-02 

P-01 

0.0 

Hz / Rpm 

P-23 

Preset Frequency / Speed 4 

P-02 

P-01 

0.0 

Hz / Rpm 

Preset Speeds / Frequencies selected by digital inputs depending on the setting of P-15 
If P-10 = 0, the values are entered as Hz. If P-10 > 0, the values are entered as Rpm. 

P-24 

2nd Decel Ramp Time (Fast Stop) 

0.00 

25.0 

0.00 

This parameter allows an alternative deceleration ramp down time to be programmed into the Optidrive, which can be selected by 
digital inputs (dependent on the setting of P-15) or selected Automatically in the case of a mains power loss if P-05 = 2. 
When set to 0.00, the drive will coast to stop. 

P-25 

Analog Output Function Select 

Digital Output Mode. Logic 1 = +24V DC  

0 : Drive Enabled (Running)

. Logic 1 when the Optidrive is enabled (Running) 

1 : Drive Healthy

. Logic 1 When no Fault condition exists on the drive 

2 : At Target Frequency (Speed)

. Logic 1 when the output frequency matches the setpoint frequency 

3: Drive Tripped

. Logic 1 when the drive is in a fault condition 

4

 

: Output Frequency >= Limit

. Logic 1 when the output frequency exceeds the adjustable limit set in P-19 

5

 

: Output Current >= Limit

. Logic 1 when the motor current exceeds the adjustable limit set in P-19 

6

 

: Output Frequency < Limit

. Logic 1 when the output frequency is below the adjustable limit set in P-19 

7

 

: Output Current < Limit

. Logic 1 when the motor current is below the adjustable limit set in P-19 

Analog Output Mode 

8 : Output Frequency (Motor Speed)

. 0 to P-01, resolution 0.1Hz 

9 : Output (Motor) Current

. 0 to 200% of P-08, resolution 0.1A 

P-26 

Skip frequency hysteresis band 

0.0 

P-01 

0.0 

Hz / Rpm 

P-27 

Skip Frequency 

0.0 

P-01 

0.0 

Hz / Rpm 

The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency which 
causes mechanical resonance in a particular machine. Parameter P-27 defines the centre point of the skip frequency band, and is used 
conjunction with P-26. The Optidrive output frequency will ramp through the defined band at the rates set in P-03 and P-04 
respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is within 
the band, the Optidrive output frequency will remain at the upper or lower limit of the band. 

P-28 

V/F Characteristic Adjustment Voltage 

250 / 500 

P-29 

V/F Characteristic Adjustment Frequency 

0.0 

P-09 

0.0 

Hz 

This parameter in conjunction with P-28 sets a frequency point at which the voltage set in P-29 is applied to the motor. Care must be 
taken to avoid overheating and damaging the motor when using this feature. See section 6.3 for further information. 
 
 
 

Содержание ODE-2-11005-1H012-01

Страница 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Страница 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Страница 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Страница 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Страница 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Страница 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Страница 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Страница 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Страница 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Страница 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Страница 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Страница 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Страница 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Страница 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Страница 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Страница 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Страница 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Страница 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Страница 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Страница 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Страница 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Страница 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Страница 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Страница 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Страница 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Страница 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Страница 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Страница 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Отзывы: