Optidrive E2 Single Phase Output User Guide V3.10

 

 

www.invertekdrives.com 

28

 

 

Tr

o

u

b

le

 Sh
oo
tin

10
 

10.

 

Trouble Shooting 

10.1.

 

Fault Code Messages 

Fault Code  Description 

Corrective Action 



Factory Default parameters 
have been loaded 

Press STOP key, drive is ready to configure for particular application 



Over current on drive output.  
Excess load on the motor. 
Over temperature on the drive 
heatsink 

Motor at constant speed: investigate overload or malfunction.  
Motor starting: load stalled or jammed. Check for star-delta motor wiring 
error. 
Motor accelerating/decelerating: The Accel/Decel time too short 
requiring too much power. If P-03 or P-04 cannot be increased, a bigger 
drive is required. Cable fault between drive and motor. 



Drive has tripped on overload 
after delivering >100% of value 
in P-08 for a period of time. 

Check to see when the decimal points are flashing (drive in overload) and 
either increase acceleration ramp (P-03) or decrease motor load. Check 
cable length is within drive specification.

 

Check the load mechanically to 

ensure it is free, and no jams, blockages or other mechanical faults exist 



Brake channel over current 

Over current in the brake resistor circuit. Check the cabling to the brake 
resistor. Check the brake resistor value. Ensure minimum resistance 
values form the rating tables are observed. 



Brake resistor overload 

Brake resistor overload. Increase deceleration time, reduce load inertia or 
add further brake resistors in parallel. Ensure minimum resistance values 
form the rating tables are observed. 



Internal power stage fault 

Check wiring to motor, look for ph-ph or ph-Earth short circuit.  Check 
drive ambient temp, additional space or cooling needed? 
Check drive is not forced into overload. 

.



Over voltage on DC bus 

Supply problem, or increase Decel ramp time P-04. 

.



Under voltage on DC bus 

This occurs routinely when power is switched off. If it occurs during 
running, check power supply voltage. 



Heatsink over temperature 

Check drive ambient temp.  Additional space or cooling required. 



Under temperature 

Trip occurs when ambient temperature is less than -10°C.  Temperature 
must be raised over -10°C in order to start the drive. 



Faulty thermistor on heatsink. 

Refer to your IDL Authorised Distributor. 



External trip  
(on digital Input 3) 

E-trip requested on digital input 3.  Normally closed contact has opened 
for some reason. 
If motor thermistor is connected check if the motor is too hot. 



Comms loss trip 

Check communication link between drive and external devices. Make 
sure each drive in the network has its unique address. 



Internal memory fault. 

Parameters not saved, defaults reloaded. 
Try again. If problem recurs, refer to your IDL Authorised Distributor. 



Analog input current out of 
range 

Check input current in range defined by P-16. 



Internal drive Fault 

Refer to your IDL Authorised Distributor. 



Internal drive Fault 

Refer to your IDL Authorised Distributor. 



Internal drive Fault 

Refer to your IDL Authorised Distributor. 

 
 
 
 
 
 
 

 

 
 
 
 



 

82-E21PH-IN_V3.10 

 

Содержание ODE-2-11005-1H012-01

Страница 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Страница 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Страница 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Страница 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Страница 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Страница 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Страница 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Страница 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Страница 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Страница 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Страница 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Страница 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Страница 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Страница 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Страница 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Страница 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Страница 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Страница 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Страница 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Страница 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Страница 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Страница 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Страница 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Страница 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Страница 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Страница 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Страница 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Страница 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Отзывы: