6.2.6.1. Terminals
Sub-group
Terminals
gathers all inputs and outputs. Depending on type of accepted
input, they are binary and analogue. Final functionality of each input depends on
settings and configuration parameters connected.
6.2.6.1.1. Inputs I1 ... I4
Module
MT-021
has four identical binary inputs. Inputs can operate in one of two
functional modes:
standard binary input
counter input
Each mode has a set of specific configuration parameters.
6.2.6.1.1.1. Name
Function
- Defines input's user friendly name
Data type
- Text
Range
- Letters and numerals, max. 16 characters
Default value
- Respective
I1
,
I2
,
I3
,
I4
Comments
- Assigning friendly names facilitates discrimination of inputs
destination and required settings.
6.2.6.1.1.2. Input type
Function
- Defines binary input's operating mode.
Data type
- Selection
list
Range
-
Binary input
Operates as binary input
Counter input
Operates as counter input
Default value
-
Binary input
Comments
- According to selected mode MTManager displays additional
configuration parameters for each input
6.2.6.1.1.2.1. Counter input
6.2.6.1.1.2.1.1. Counting direction
Function
- defines
counting direction
Data type
- selection
list
Range
-
Up
A pulse on input increases value of counter register
Down
A pulse on input decreases value of counter register
Default value
-
Up
Comments
- N/A