74
Parameter
MTManager description
Default
value
Range
Definition
OUT_OFFEVT_* Off
event
0
0
1
...
16
None
EVT1
...
EVT16
(* - index from 1
to 16)
Analog inputs AN1, AN2 * - index from 1 to 2
AN_NAME_
*
Name
AN*
max. 16 characters
AN_MODE_* Input
type
1
1
2
3
Voltage input
Current input
PT100 (AN1) or
NTC (AN2)
AN_FLR_*
Filtering constant [s]
0
0
1
2
3
4
5
6
7
8
0
0,05
0,1
0,25
0,5
1
2
4
8
AN_RANGE_* Signal
range
1
0
1
0...5V
0...10V
AN_LREF_*
Low reference - internal units
{0...5V}
0 0...500
AN_LREF_*
Low reference - internal units
{0...10V}
0 0...1000
AN_LREF_*
Low reference - internal units
0
0...2000
AN_HREF_*
High reference - internal units
{0...5V}
1000 0...500
AN_HREF_*
High reference - internal units
{0...10V}
1000 0...1000
AN_HREF_*
High reference - internal units
1000
0...2000
AN_LENG_*
Low reference - engineering
units
0 -32757...32767
AN_HENG_*
High reference - engineering
units
1000 -32757...32767
AN_ALM_HH_*
Alarm HiHi - engineering units
32767
-32757...32767
AN_NAME_
*
Name
AN*
max. 16 characters
AN_ALM_HI_*
Alarm Hi - engineering units
32767 -32757...32767
AN_ALM_LO_*
Alarm Lo - engineering units
-32767
-32757...32767
AN_ALM_LL_*
Alarm LoLo - engineering units
-32767
-32757...32767
AN_ALM_HIST_
*
Alarm hysteresis - engineering
units
100 0...65535
AN_DBD_*
Deadband - engineering units
100
0...65535
1-Wire inputs (1, 2) * - index from 1 to 2
OW_NAME_
*
Name
1-WIRE*
max. 16 characters
OW_ACT_* Input
mode
1
1
2
Inactive
Temperature
measurement
OW_ALM_HH_* Alarm
HiHi
125
-25...125
OW_ALM_HI_* Alarm
Hi
125
-25...125
OW_ALM_LO_* Alarm
Lo
-25
-25...125
OW_ALM_LL_* Alarm
LoLo
-25
-25...125
OW_ALM_HIST_
*
Alarm hysteresis
2
0...50
OW_DBD_* Deadband
2
0...50
Содержание MT-021