44
6.2.6.1.3. Analog inputs AN1...AN2
MT-021
module is equipped with two analog inputs operating in 4...20mA or
0...5V/0...10V standard and direct measurement of the temperature sensor PT100
(AN1) or NTC (AN2).
Each mode has a set of specific configuration parameters.
6.2.6.1.3.1. Name
Function
-
Defines input's user friendly name
Data type
- Text
Range
-
Letters and numerals, max. 16 characters
Default value
- Respectively
(
AN1,
AN2
)
Comments
-
Assigning friendly names facilitates discrimination of
inputs destination and required settings.
6.2.6.1.3.2. Input type
Function
- selection of analog input mode
Data type
- selection list
Range
-
Voltage input
signal measurement 0..10V or 0..5V depending on selected
setting
Current input
signal measurement 4..20mA
Pt100
temperature measurement by PT100 sensor (available for
AN1)
NTC
temperature measurement by NTC sensor (available for
AN2)
Default value
-
Voltage input
Comments
- N/A
6.2.6.1.3.3. Filtering constant [s]
Function
- defines (in seconds) the value of the measurement averaging
time of analog input
Data type
- selection list
Range
-
0, 0.05, 0.1, 0.25, 0.5, 1, 2, 4, 8
Default value
-
0
Comments
- N/A
6.2.6.1.3.4. Signal range
Function
- selection of voltage analog input range
Data type
- selection list