11
3.7. Resources
MT-021
module's resources:
I1...I4
- binary inputs
4
Optoisolated binary inputs
Q1...Q4 -
Relay outputs
4
Relay outputs can operate in one of
two functional modes:
monostable
bistable
CNT
- Counters
0 (max. 4)
Each input can work as a counter input
AN1, AN2
- Analog inputs
2
PT100
NTC
0..10V/0..5V
4-20mA
1-Wire
- Inputs
2
Standard Dallas I-Button,
Temperature measurement
USB Port
1
Standard RS232 - configuration
3.7.1. Binary inputs
MT-021
module is equipped with 4 optoisolated binary inputs marked as I1...I4. They
may work only in positive logic. All binary inputs have same reference - module's
electrical ground - negative pole of the power supply connected to GND pin.
The change of the input signal sets the alarm flag, connected with the corresponding
binary input respectively as Bi 0->1, Bi 1->0 or Bi 0->1|Bi 1->0.