42
6.2.6.1.1.2.1.2. Counting range (32bits)
Function
-
defines max. value assumed by the counter
Data type
- number
Range
-
0....2 147 483 647
Default value
-
0
Comments
- N/A
6.2.6.1.1.2.1.3. Triggering slope
Function
-
selects counting direction
Data type
- selection
list
Range
-
Bi 0->1
The change of counter state occurs upon signal change
from 0 > 1
Bi 1->0
The change of counter state occurs upon signal change
from 1 > 0
Bi 0->1 | 1->0
The change of counter state occurs upon any change of
signal
Default value
-
Bi 0->1
Comments
- N/A
6.2.6.1.1.3. Filtering constant [s]
Function
-
Defines (in seconds) value of minimum duration of
altered state on input in order to consider state to be
stable.
Data type
- number
Range
-
0....163,83 [s]
Default value
-
0,10 [s]
Comments
-
Setting value appropriate to contact characteristics
eliminates disturbance caused by contact bounce thus
preventing multiple registration of what is in reality one
pulse.
6.2.6.1.2. Outputs Q1 ... Q4
The
MT-021
module is equipped in four relay outputs Q1...Q4. Outputs can operate in
one of two functional modes:
monostable
bistable
Each mode has a set of specific configuration parameters.