5.3.6 Radio operation
Repeater enable:
EnOcean repeater function enablement.
Repeater level:
EnOcean repeater function mode, if repeater is disabled, this parameter is
not significant. It can be configured as:
-
Disabled: no telegrams will be repeated.
-
1-LEVEL: original telegrams will be repeated.
-
2-LEVEL: original and repeated telegrams will be repeated.
IR disablement:
disablement of the AC remote control. If this value is true, AC remote
control will be overridden by the gateway.
5.4 Default values
Parameter
Default value
Units
Machine mode
NORMAL <enum>
Threshold ambient temperature cool
26 ºC
Threshold ambient temperature heat
21 ºC
Min. setpoint cool
24 ºC
Max. setpoint cool
28 ºC
Min. setpoint heat
19 ºC
Max. setpoint heat
23 ºC
Wake up time
120 seconds
Window reload last value
False <bool>
Window lock when open
True <bool>
Window timeout
1 minutes
Key card reload last value
False <bool>
Key card lock when not inserted
True <bool>
Occupancy duration
40 seconds
Occupancy 1
st
action timeout
10 minutes
Occupancy 1
st
action
APPLY _DELTA <enum>
Occupancy 1
st
action delta heat
-2 ºC
Occupancy 1
st
action delta cool
2 ºC
Occupancy 2
nd
action active
True <bool>
Occupancy 2
nd
action timeout
30 minutes
Occupancy 2
nd
action
SWITCH_OFF <enum>
Occupancy 2
nd
action delta heat
-3 ºC
Occupancy 2
nd
action delta cool
3 ºC
Occupancy reload last value
False <bool>
Occupancy lock when unoccupied
False <bool>
Input 1..4 inverted
False <bool>
Input 1..4 function
NONE <enum>
Input 1..4 key card
False <bool>
Repeater enable
False <bool>
Repeater level
Disabled <enum>
IR disablement
False <bool>
Table 5.1
Default values