12. AC profile data (Generic HVAC interface)
In this section the
Generic HVAC interface
EEPs (07-20-10 and 07-20-11) applied to the
IntesisBox
®
are explained. These two EEPs along with the
Room Operating Panel
EEP 07-
10-03 can transmit and receive all the AC information.
Following description will only apply for profiles E and F.
12.1 EEP: 07-20-10
ORG = 07 (4 BS)
FUNC = 20 (HVAC Components)
TYPE = 10 (Generic HVAC interface
–
Functions: Mode, vane position, fan speed, sensors and on/off)
EEP for Generic HVAC interface
–
Functions: Mode, vane position, fan speed, sensors and on/off: With this EEP plus
the already existing EEP 07-10-03 and 07-20-11 all the information of AC indoor unit can be sent and received
allowing a much easier and complete control of these units.
Teach-In
The teach-in telegram has the same structure as a normal 4BS telegram.
See EnOcean Equipment Profiles (EEP) v2.1 and use the following structure.
DB_3.7 ... DB_3.2:
Function: same as teach-in telegram heating valve = 20
DB_3.2 ... DB_2.3:
Type: same as teach-in telegram actuator = 10
DB_2.2 ... DB_1.0:
Manufacturer: Intesis Software ID = 0x019
DB_0.7:
LRN TYPE = 0b1 (type 1 with profile, manufacturer Id)
DB_0.6:
EEP result; EEP supported = 0b1, EEP not supported = 0b0
DB_0.5:
LRN result; ID stored = 0b1, ID deleted (not stored ) = 0b0
DB_0.4:
TA: teach-in answer = 0b1
DB_0.3:
LRN Learn button
0b0 Teach-in telegram
0b1 Data telegram
DB_0.2 ... DB_0.0:
Not used